Entes MPR-53CS Скачать руководство пользователя страница 4

NETWORK ANALYZER

MPR-53CS

Latch menu:

When latch function of set parameters is active, user can choose the way 

how to fault recovery in this menu. User can make this by 3 ways.

LAt Ch bUt ton: 

Removal of latch is chosen by pressing the “SET” 

button. By chosing “oFF”, SET button becomes passive. 

LAt Ch ın PUt: 

Fault recovery can be done with using digital inputs.

When “LAt Ch ın I-2” is chosen only second digital input becomes 

active. 

When “LAt Ch ın ALL” is chosen both of the digital inputs become 

active. 

User can remove the latch when the signal comes to digital inputs. 

When “LAt Ch ın oFF” is chosen this feature becomes pasive.

LAt Ch AUto:

 When this feature is chosen fault recovery occurs at the 

end of the set time. User can set the turning time below.  

 

User can choose the time between 15 min. - 180 min.. Time can be set by 

multiples 15 (15, 30, 45, 60, 75, 90, 105, 120,135, 150, 165 or 180 min.).

NOTE: “LAt Ch bUt ton”, “LAt Ch ın PUt” ve “LAt Ch AUt o” can be 

activated at the same time. 

Press SET button for 3 sec. (trA Fo menu is displayed.)

menu.

Press SET button (LAt Ch bUt ton menu is displayed.)

By using UP/DOWN buttons, from the menus of “LAt Ch bUt ton/

ın PUt/AUt o” choose the menu where the setting will be done.

Press SET button (on/oFF/oFF is displayed).

By using UP/DOWN buttons, select related parameter values  (”on”, 

“oFF”/ “oFF”, “I-1”, “I-2”, “ALL” / “oFF”, “15 ... 180”). 

Press SET button, “LAt Ch bUt ton/ın PUt/AUt o” is displayed.  (Option is 

entered but is not activated yet. For activating the new data please follow 

the below steps.)
Press ESC button one by one until “SAU E SEt yES” is displayed.

When “SAU E SEt yES” is displayed, press SET button. If you press ESC 

button or choose “no” option instead of “yES” option by using UP/DOWN 

buttons, new data will be cancelled and previous value will be activated.

Pulse Counter (PUL SE CoU ntE r)

PUL C-1 ACt: In this menu, the activation of C-1 counter is done. If “on” is 

chosen C-1 counter will be active, and if “oFF” is chosen C-1 counter will 

become passive. 

counters is set same way.

Example :

 If the ratio of the C-1 counters is 10, every 10 pulses come 

from In-1 input the counter counts 1.

Note: DC signal has to be given to the digital inputs when this menu is 

used. When AC signal is given, pulse counter counts according to the 

given sources frequency.

Note: If “ACt oFF” is chosen for C-1 and C-2 counters, the pulse 

counting feature will become passive. In instant values, passive 

counter is not displayed.

Press SET button for 3 sec. (trA Fo menu is displayed)

“PUL SE CoU ntE r”menu

Press SET button (PUL C-1 ACt menu is displayed).

By using UP/DOWN buttons, from the menus of “PUL C-1 ACt/

C-1 rAt ıo/C-2 ACt/C-2 rat ıo” select the menu.

Press SET button (on/9999/on/9999 is displayed).

By using UP/DOWN buttons and select interested parameter values (“on-

oFF”/“0001...9999”/”on-oFF”/“0001...9999”).

Press SET button, “PUL C-1 ACt/C-1 rAt ıo/C-2 ACt/C-2 rat ıo” is dis-

played. (Option is entered but is not activated yet. For activating the new 

data please follow the below steps.)
Press ESC button one by one, until “SAU E SEt yES” is displayed.
When “SAU E SEt yES” is displayed, press SET button. If you press ESC

 

button or choose “no” option instead of “yES” option by using UP/

DOWN buttons, new data will be cancelled and previous value will 

be activated.

Hour menu:

In this menu run hour and setpoint hour is set.

“hoU r ACT”:

 In this menu the run hours activation conditions are set.

 When “hoU r ACT on” is chosen, the run hour keeps working uncondi-

tionally.

is active.

 When “hoU r ACT ı-2” is chosen, the run hour runs if second digital input 

is active.

 When “hoU r ACT ALL” is chosen, the run hour runs if one of the digital 

inputs is active.  

“hoU r SP” :

 In this menu, alarm time is set. When the set time reaches 

“SP -h” chosen output will be active.

Between 0001 - 9999 the hours can be set.

“hoU r oUt” : 

In this menu the alarm output is chosen. It can be chosen 

between 1 ... 8. First and second outputs are relay outputs 3. ... 8 outputs 

are digital outputs. 

Press SET button for 3 sec. (trA Fo menu is displayed)

Press SET button (”hoU r SP” menu is displayed.)

Press SET button (”hoU r SP 000 0” is displayed)

By using UP/DOWN buttons, enter the values for blinking digits. By 

using SET button, other digits in turn, by using BACK button for previous 

menu. When last digit is programmed press SET button, “hoU r SP” is 

displayed.

By using UP/DOWN buttons from the menus of “hoU r ACT/oUt”

select the menu.

Press SET button (on/1 displayed).

By using UP/DOWN buttons set the related parameters values (”on”, 

“ı-1”, “ı-2”, “ALL” / “1 ... 8”).

Press SET button, “hoU r ACT/oUt” is diplayed (Option is entered but is 

not activated yet. or activating please follow the below steps).

Press ESC button one by one until “SAU E SEt yES” is displayed.

When “SAU E SEt yES” is displayed, press SET button. If you press ESC 

button or choose “no” option instead of “yES” option by using UP/DOWN 

buttons, new data will be cancelled and previous value will be activated.

Setpoint menu:

In this menu setpoint setting can be programmed. In this menu there 

are 16 setpoint setting (SP -01 ... SP -16). “SP -xx ACt” menu must be 

activated from the chosen setpoint menu. If not, user can not enter the 

“SP -xx” parameters.

“SP -01 ... SP -16” 

: 16 setpoint settings which are set by the user. “SP-

01” protection setting activation and settings of the sub menu parameters 

are given below. All other setpoint protection settings can be done by 

same way.

“SP -01 ACt”

 : In this menu “SP -01” protection settings is done. When 

protection setting is chosen “oFF”, SP -01’s other menus can not be 

reached.

      “SP -01 ACt on”: Protection setting is active.

      “SP -01 ACt oFF”: Protection setting is passive. 

one of these parameters can be setted.

Note : 

Protection settings parameters and the information are in the 

attachement.

“SP -01 oPE” :

 In this menu, extreme, low or both protection settings are 

determined. Sub menus are explained below.

      “SP -01 oPE rAn gE”: Low, extreme protection is done. 

      “SP -01 oPE hıg hEr”: Extreme protection is done. 

      “SP -01 oPE LoU Er”: Low protection is done.

“SP -01 hı” : 

In this menu extreme protection value is set. 

 

“SP -01 Lo”:

 In this menu low protection value is set. 

Note: When extreme protection value is chosen low protection 

value is closed, and when low protection value is chosen extreme 

protection value is closed in “SP -01 oPE” menu.

“SP -01 hYS” : 

In this menu fault recovery hysteresis value is set.

“SP -01 ond” : 

In this menu entering the fault delay is set 

(000.0-999.9 sec.).

“SP -01 oFd” : 

In this menu fault recovery is set (000.0-999.9 sec.).

“SP -01 oUt” : 

In this menu alarm output is chosen. 1. ... 8. outputs can 

be chosen. First and the second outputs are relay outputs, the others (3. 

... 8) are digital outputs.

“SP -01 LAt Ch”: 

In this menu lock function is activated. 

      “SP -01 LAt oFF”: Closes the latch function.  

      “SP -01 LAt on”: Activates the latch function. 

Note: Latch functions are set in latch menu.

Note: When protection parameters give error the user can see the 

erroneous parameter by using UP/DOWN buttons in instant values 

(more than one error use SET button).

4

Содержание MPR-53CS

Страница 1: ...selected 1 out 1 and 2 out 2 for output device gives alarm Related contact outputs will close and LEDs will be on Total Hours Shows running time of MPR 53CS from the beginning User can not reset this...

Страница 2: ...will be cancelled and previous value will be activated NETWORK ANALYZER MPR 53CS Current Transformer Ratio Setup In this menu current transformer ratio is set There is no in CT 25 models Current tran...

Страница 3: ...s Press ESC button one by one until SAU E SEt yES is displayed When SAU E SEt yES is displayed press SET button If you press ESC button or choose no option instead of yES option by using UP DOWN butto...

Страница 4: ...onditions are set When hoU r ACT on is chosen the run hour keeps working uncondi tionally is active When hoU r ACT 2 is chosen the run hour runs if second digital input is active When hoU r ACT ALL is...

Страница 5: ...tandart MODBUS RTU message is shown below The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one mes...

Страница 6: ...BY USING REPEATER PK 26 Box Connection Diagram 3 Phase neutral 3 Phase without neutral Note For CT 25 models k When CT 25 is used Red cable is connected to k terminal l When CT 25 is used Black cable...

Страница 7: ...e neutral 3 Phase without neutral Note For CT 25 models k When CT 25 is used Red cable is connected to k terminal l When CT 25 is used Black cable is connected to l terminal 3 Phase without neutral cu...

Страница 8: ...Settings Transformer Ctr Current Transformer Ratio 0001 trn Turn number for CT 25 01 Utr Voltage Transformer Ratio 0001 0 CAL Calculation Method 1 Pin 0000 Not Activated RS 485 Adr Address 1 Bau Baud...

Страница 9: ...al in digital inputs It does not run if there is no signal in digital inputs Betriebsstunden Es zeigt die Betriebsstunden Im Gegensatz zu der Gesamtstunden k nnen die Betriebsstunden r ckgestellt und...

Страница 10: ...hlt werden Dr cken Sie auf SET Taste f r 3 Sekunden trA Fo Men ist angezeigt Dr cken Sie auf SET Taste TrA Fo Ctr Men ist angezeigt Sie das CAL CUL At on Men blinkelt Mit AUF oder AB Tasten w hlen Si...

Страница 11: ...n aber sind noch nicht aktiviert F r die Aktivierung der eingegebenen Daten befolgen Sie die folgende Schritten Dr cken Sie auf ESC Taste bis SAU E SEt yES ist angezeigt Dr cken Sie auf SET Taste W hr...

Страница 12: ...oUr ACt 1 ausgew hlt ist funktioniert die Betriebsstunden nur wenn der Digitaleingang 1 aktiv ist Falls hoUr ACt 2 ausgew hlt ist funktioniert die Betriebsstunden nur wenn der Digitaleingang 2 aktiv i...

Страница 13: ...Zeit zwischen 3 5 Zeichen Zeit in denen keine Daten ber die Kommunikations Bus ausgetauscht werden m ssen damit die angeschlossenen Ger te die Ende einer Nachricht und dem Beginn eines anderen zu erk...

Страница 14: ...HLIESSEN PK 26 Kassenanschlussplan 3 Phasen ohne Neutral Anschluss Nur g ltig f r MPR 53S k Wenn CT 25 benutzt ist rotes Kabel ist an der Klemme k angeschlossen l Wenn CT 25 benutzt ist schwarzes Kabe...

Страница 15: ...Kassenanschlussplan 3 Phasen mit Neutral Anschluss 3 Phasen ohne Neutral Anschluss Nur g ltig f r MPR 53S k Wenn CT 25 benutzt ist rotes Kabel ist an der Klemme k angeschlossen l Wenn CT 25 benutzt i...

Страница 16: ...gen Die Nichteinhaltung dieser Anweisungen f hrt zu schweren Verletzungen oder zum Tod Vor der Installation entfernen Sie die Leistungsenergie an den Ger ten Wenn das Ger t an das Netzwerk verbindet i...

Отзывы: