NETWORK ANALYZER

MPR-53CS 

General

MPR-53CS measures all the electrical parameters that belong to network. MPR-

53CS is designed for protection of electrical system. Measured parameters are 

shown in 5 separate displays. This allows to monitor more than 50 parameters at the 

same time. MPR-53CS has also MODBUS serial interface feature. 

The table below shows the parameters that are measured by MPR-53CS:

Functions of Buttons

Used for switching between (VLN, VLL, A, W, VAr, VA, Cos   , kWh, 

kVarh, THD, C-1, C-2, tot-h, run-h) parameters in the monitoring 

mode. 

Used for switching between previous ( ) or next ( ) menu in main 

menu or submenus and also use for changing chosen values. 

(SET) Used for switching between min., max demand and instant 

values in the monitoring mode. In display when run hour (run -h) is 

displayed, if SET button is pressed, it shows setpoint hours 

(SP -h) counted time. In latch function when button feature is used, 

with SET button latch position operation is done. Switching to the 

programming mode if it pressed for 3 sec. It is used for switching to the 

menu and saving changes for the parameters in programming mode. 

(Back) Used for switching between SW, SVA and Hz parameters in the 

monitoring mode. Used for switching previous digit in submenu.

(ESC) Used for switching between SVAr and Cos   values in the 

monitoring mode. Used for entering to upper menu or it is used to quit 

from the programming mode without saving values in the programming 

mode. 

When Pin is activated, after pressed “SET” button for 3 seconds, PIN is 

required; after entering correct PIN code, you can enter to menu. 

Use of MPR-53CS:

By using Up/Down buttons parameters are shown in L1, L2, L3 displays (VLN; VLL; 

A; IN; W; VAr; VA; Cosj; kWh, kVarh, THD, C-1, C-2, tot-h, run-h). Total Active (SW), 

Total Apparent Power (SVA) and Frequency (Hz) are selected by Back button.

Total Reactive Power (SVAr) and Cos   are selected by Esc button. 

Digital Inputs

MPR-53CS has 2 digital inputs. Digital inputs have 2 functions :   

- If remote control is activated (battery, thermostat, circuit breaker, engines status) 

the status of devices connected to digital input will be seen according to datas in 

time regiters. 

- When digital inputs of energy count, run hour and latch menus are selected, digital 

inputs controls these menu’s functions (

Example: 

It is used for measuring of energy

separately at the using of network and generator). 

aren’t any signal in digital inputs. Otherwise “on”. 

Energy Pulse Outputs

MPR-53CS has 2 energy pulse outputs. Pulse outputs give the pulses only for 

E-1 (energy counter). Pulse outputs can be programmed one by one. When pulse 

outputs give pulse “P1” (Pulse 1) and “P2” (Pulse 2) lights (Not included in the PK-26 

Pul1 ve Pul2 : 

There are sub menus o-1 (pulse 1) and o-2 (pulse 2) in pulse out 

menu. Device gives pulse according to chosen energy parameters [Active energy 

(ACt, A-I, A-E), Reactive energy (rEA, r-L, r-C)]. For energy count values, look at 

the pulse menu.

Pulse Counter

MPR-53CS has 2 pulse counters (C-1, C-2). C-1 counts the pulses from digital input 

1 and C-2 counts the pulses from digital input 2. 

Pulse counter detect the pulses which are in condition of signal 1. When the number 

of pulses reach “pulse C1/2 ratio” value, releated pulse counter is increase by 1. 

When C-1/C-2 counters are not activated in pulse counter menu, instant values of 

C-1/C-2 are not displayed.

Note: DC signals must be use supplied in order to use this menu. 

Digital Outputs 

MPR-53CS has 6 digital outputs. Only 2 of them have LED on the front panel. These 

are “O-3” and “O-4” LEDs (“O-4” light is not available in the PK-26 box).

When digital outputs are activated, related addresses can be displayed with “xxx” 

values, only “O-3” and “O-4” LEDs are lighted for digital outputs 1 and 2 on front 

panel. Digital output on devices menu’s output parameters;  1/2/3/4/5/6 correspond 

to “3/4/5/6/7/8” parameters. 

User can check the digital output register for fault about set parameters by 

communicating with the device. 

Relay Outputs 

MPR-53CS has 2 NO contact outputs. On front panel, MPR-53CS has 

o-1 and o-2 LEDs. When alarm parameters are selected 1 (out 1) and 2 

(out 2) for output, device gives alarm. Related contact outputs will close and LEDs 

will be on. 

Total Hours

Shows running time of MPR-53CS from the beginning. User can not reset this 

counter.

Run Hours

Shows MPR-53CS’s running hour. This can be resetted and can be controlled by 

it runs if there is a signal in digital inputs. It does not run if there is no signal in digital 

inputs.

Setpoint Hours

By pressing SET button during monitoring of Run Hour, set point hour can be 

monitored. Setpoint hour runs according to run hour. When run hour runs actively, 

setpoint hour runs. When set time value reaches to “hoU r SP” which set by user, 

selected output will be active (1) and give an alarm and setpoint hour continues to 

count. This alarm can be erased by resetting setpoint hour or getting out from locked 

position. When setpoint output is required to remove by using latch function, “latch 

auto” function can’t be used. If MPR-53CS returned to normal operation from failure 

by using latch function, it automatically starts the time from zero. To make setpoint 

hour passive, the value of SP hour is set “0000”. This setting only closes the setpoint 

Note: 

Total hour and run hour do not count during electric interruptions. Total hour 

measurement mode, by scrolling UP and DOWN buttons, user can see running 

time. Run hour display is shown is “HH HHH H.HH” (H=Hour) form. All the values 

shown on the display are in terms of hour. For example, if displayed value is 00 000 

1.75, means that device worked for 1.75 hours. If the user wants to convert last digit 

to minutes, last digitx0.6 (75x0.6=45 minutes) formula is used conversion. Device 

worked 1 hour 45 minutes. 

İmportant: 

In “hoU r SP” menu when chosen output is activated and devices is set 

for giving an alarm at the end of one hour. After counting to 99 on display, devices 

gives an alarm (1 hour = 60 min. for MPR-53CS on display “99” corresponds to “59”). 

Monitoring of Min.- Max. and Max. Demand Values:

LN

, V

LL

, A, W, VAr, VA,  W,  VAr,  VA; 

W,  VA,  VAr.

If measured instant value is smaller than min. value, they are saved as new min. and 

if measured instant value is bigger than instant max. value, new max. value is saved. 

During demand time (example 15 min.) demand value is got max. demand.

If press SET button when the device is in any parameter (example “A”) min., max. 

parameter (example “Cos  ”) is displayed, the device continues to display instant 

parameters.

Monitoring THD Values

If “VLN” and “THD” LED’s light on together, voltage “THD” is monitored. And if “A” 

and “THD” LEDs light on, current “THD” is monitored. 

Monitoring Neutral Current

When instant current values of 3 phases are shown on the display, by pressing the 

“DOWN” button, I-n (neutral current) is displayed. “A” LED continues light on. When 

connection form is chosen as delta, this display will be closed.

Monitoring Setpoint Parameters Fault Warning

Device activates the selected output if there is a failure because of any causes. 

User can set more then one parameters to output, so outputs can be monitored 

depending which parameter and this parameters protection type (low, high, both of 

them) even in failure situation when “rUn -h” menu is displayed, pushing “DOWN” 

button or when VLN is displayed pushing “UP” button, failure parameter  will be seen 

as “SP -xx h/L/hL x-x x-x”. If there is a no failure, you will not see such a display. 

After pressing SET button you can see other failure parameter. 

Calculation Methods for Active / Reactive Values

If the dot on the right down corner blinks it shows that active power and reactive 

powers directions are negative. There are 2 methods for calculating total active and 

total reactive powers.

1) Active and reactive powers are calculated by summing import and export values 

and shown as a single value. 

2) Active and reactive powers are calculated one by one according to import/export 

condition.

Note :

1) During  W LED is displayed, if the dot at the most right down digit of the forth 

display lights on, it represents that displayed value is export active power value. 

If not, it represents that displayed value is import active power value.

2) During 

display lights on, it represents that displayed value is capacitive reactive power 

value. If not, it represents that displayed value is inductive reactive power value. 

stand by.

1

Содержание MPR-53CS

Страница 1: ...selected 1 out 1 and 2 out 2 for output device gives alarm Related contact outputs will close and LEDs will be on Total Hours Shows running time of MPR 53CS from the beginning User can not reset this...

Страница 2: ...will be cancelled and previous value will be activated NETWORK ANALYZER MPR 53CS Current Transformer Ratio Setup In this menu current transformer ratio is set There is no in CT 25 models Current tran...

Страница 3: ...s Press ESC button one by one until SAU E SEt yES is displayed When SAU E SEt yES is displayed press SET button If you press ESC button or choose no option instead of yES option by using UP DOWN butto...

Страница 4: ...onditions are set When hoU r ACT on is chosen the run hour keeps working uncondi tionally is active When hoU r ACT 2 is chosen the run hour runs if second digital input is active When hoU r ACT ALL is...

Страница 5: ...tandart MODBUS RTU message is shown below The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one mes...

Страница 6: ...BY USING REPEATER PK 26 Box Connection Diagram 3 Phase neutral 3 Phase without neutral Note For CT 25 models k When CT 25 is used Red cable is connected to k terminal l When CT 25 is used Black cable...

Страница 7: ...e neutral 3 Phase without neutral Note For CT 25 models k When CT 25 is used Red cable is connected to k terminal l When CT 25 is used Black cable is connected to l terminal 3 Phase without neutral cu...

Страница 8: ...Settings Transformer Ctr Current Transformer Ratio 0001 trn Turn number for CT 25 01 Utr Voltage Transformer Ratio 0001 0 CAL Calculation Method 1 Pin 0000 Not Activated RS 485 Adr Address 1 Bau Baud...

Страница 9: ...al in digital inputs It does not run if there is no signal in digital inputs Betriebsstunden Es zeigt die Betriebsstunden Im Gegensatz zu der Gesamtstunden k nnen die Betriebsstunden r ckgestellt und...

Страница 10: ...hlt werden Dr cken Sie auf SET Taste f r 3 Sekunden trA Fo Men ist angezeigt Dr cken Sie auf SET Taste TrA Fo Ctr Men ist angezeigt Sie das CAL CUL At on Men blinkelt Mit AUF oder AB Tasten w hlen Si...

Страница 11: ...n aber sind noch nicht aktiviert F r die Aktivierung der eingegebenen Daten befolgen Sie die folgende Schritten Dr cken Sie auf ESC Taste bis SAU E SEt yES ist angezeigt Dr cken Sie auf SET Taste W hr...

Страница 12: ...oUr ACt 1 ausgew hlt ist funktioniert die Betriebsstunden nur wenn der Digitaleingang 1 aktiv ist Falls hoUr ACt 2 ausgew hlt ist funktioniert die Betriebsstunden nur wenn der Digitaleingang 2 aktiv i...

Страница 13: ...Zeit zwischen 3 5 Zeichen Zeit in denen keine Daten ber die Kommunikations Bus ausgetauscht werden m ssen damit die angeschlossenen Ger te die Ende einer Nachricht und dem Beginn eines anderen zu erk...

Страница 14: ...HLIESSEN PK 26 Kassenanschlussplan 3 Phasen ohne Neutral Anschluss Nur g ltig f r MPR 53S k Wenn CT 25 benutzt ist rotes Kabel ist an der Klemme k angeschlossen l Wenn CT 25 benutzt ist schwarzes Kabe...

Страница 15: ...Kassenanschlussplan 3 Phasen mit Neutral Anschluss 3 Phasen ohne Neutral Anschluss Nur g ltig f r MPR 53S k Wenn CT 25 benutzt ist rotes Kabel ist an der Klemme k angeschlossen l Wenn CT 25 benutzt i...

Страница 16: ...gen Die Nichteinhaltung dieser Anweisungen f hrt zu schweren Verletzungen oder zum Tod Vor der Installation entfernen Sie die Leistungsenergie an den Ger ten Wenn das Ger t an das Netzwerk verbindet i...

Отзывы: