“CAL CUL Atı on” menu.

Press SET button (Most right digit of 5th display blinks)

By using UP/DOWN buttons select energy calculation method. 

Press SET button, “CAL CUL Atı on” is displayed. (Data is entered but is 

not activated yet, for activating new data please follow below steps.)

Press ESC button one by one until “SAU E SEt  yES” is displayed. 

When “SAU E SEt yES” is displayed, press SET button (When “SAU E 

SEt yES” is displayed. If you press ESC button or choose “no” option 

instead of “yES” option, new data will be cancelled and previous value 

will be activated).

Max. Demand Time Setup: 

In this menu, Max. demand time is set between 01 - 60 minutes.

Press SET button for 3 sec. (trA Fo menu is displayed.) 

Press SET button (Most right digit of 5th display blinks) 

By using UP/DOWN buttons, blinking digit value can be programmed. 
By using SET button, switch respectively to the digits. Use BACK button 

go to go previous digit. After you entered last digit, press SET button, 

“de tı” is displayed in the display. (Data is entered but is not activated 

yet. For activating new data please follow the below steps.) 

Press ESC button one by one until “SAU E SEt  yES” is displayed. 

When “SAU E SEt yES” is displayed, press SET button (When 

“SAU E SEt yES” is displayed. If you press ESC button or choose “no” 

option instead of “yES” option, new data will be cancelled and previous 

value will be activated).

Reset Menu (hL, dE, E-1, E-2, C-1, C-2, rUn hoUr, SP hoU r):

In this menu value of min., max., max. demand, energy values, pulse 

counters, run hour and alarm clock are erased. It saves the instant 

measured min., max., max. demand energy values, the devices running 

time, time after the device is setted into its memory. In this menu when 

you enter “rES Et hL/dE/E-1/E-2/C-1/C-2/rUn hoUr/SP hoU r” menu 

changes all the values are erased at the same time.

Note: 

from power cut. 

Reset Menu (hL, dE, E-1, E-2, C-1, C-2, rUn hoUr, SP hoU r):

Press SET button for 3 sec. (trA Fo menu is displayed.) 

Press SET button (rES Et hL menu is 

displayed.) 

By using UP/DOWN buttons “rES Et hL/dE/E-1/E-2/C-1/C-2/

rUn hoU r/SP hoU r” menu.

Press SET button (rES Et hL/dE/E-1/E-2/C-1/C-2/rUn hoU r/ 

SP hoU r is displayed).
By using UP/DOWN buttons, if you want to delete, the min., max., max. 

demand, energy values, the running time of the device and the running 

time after the device is set; select “yES” otherwise select “no” option.

Press SET button, “rES Et hL/dE/E-1/E-2/C-1/C-2/rUn hoU r/SP hoU r” 

is displayed. (Data is entered but is not activated yet. For activating new 

data please follow the below steps)
Press ESC button one by one until “SAU E SEt  yES” is displayed.

When “SAU E SEt yES” is displayed, press SET button (When “SAU E 

SEt yES” is displayed. If you press ESC button or choose “no” option 

instead of “yES” option, new data will be cancelled and previous value 

will be activated).

NETWORK ANALYZER

MPR-53CS

Current Transformer Ratio Setup:

In this menu current transformer ratio is set (There is no in CT-25 

models). 

Current transformer ratio can be set between 1 ..... 2000. 

Note: If the current transformer is not used between the system and the 

device, current transformer ratio is entered as “1”.

Example: If between the device and the system there is a 30A/5A current 

transformer is used;

Current transformer ratio = 30/5 = 6 must be setup.

Press SET button for 3 sec. (trA Fo menu is displayed)

Press SET button, trA Fo Ctr menu is displayed (For CT-25 models 

trA Fo trn menu is displayed).

(Note: trA Fo Utr / Con nEC tıo n menu can be displayed by scrolling UP/

DOWN buttons.) 

(trA Fo Utr or Con nEC tıo n menus can be programmed similarly.) 

Using the UP/DOWN buttons and program the blinking digit. Switch 

to other digits by using SET button, use BACK button to go topevious 

digit. After programming last digit press SET button,  “trA Fo Ctr” is 

displayed. (Data is entered but is not activated yet. For activating new 

data please follow the below steps.) 

 

Press ESC button one by one until “SAU E  SEt  yES” is displayed on 

display. 

When “SAU E SEt yES” is displayed, press SET button. If you press ESC 

button or choose “no” option instead of “yES” option by using UP/DOWN 

buttons, new data will be cancelled and previous value will be activated. 

Entering Turn Number:

This menu is available for CT-25 adapted devices. Turn number is chosen 

from CT-25 current transformer (How many tour the current cable has 

rounded). The values between 1 and 20 can be written. Greater the 

number of turn means greater the sensivity.

Voltage Transformer Ratio Setup: 

In this menu, voltage transformer ratio setup is set.

Voltage Transformer ratio is set between 0000,1 - 4000,0.

Note: 

 If the voltage transformer is not used between the system and the 

device. The voltage transformwer ratio is entered as “1”.

Example: 

Between the voltage transformer and the device, if there is a 

34,5KV/100V voltage transformer is used; 

Voltage transformer ratio =  34500/100  = 345 can be entered. 

Chosing connection option:

In this menu connection option is selected. There are 2 option as  

“delta” and “star”.

When “Star” connection is chosen, the device makes a protection  

between phase-neutral for voltage.

When “Delta” connection is chosen, the device makes a protection  

between phase-phase for voltage.

NOTE: When “Delta” is chosen Neutral Current (I

N

) and 

Phase-Neutral Voltage (V

LN

) values can not be shown in instant 

values. Functions that belong to this parameters are inactive.

Reactive Energy Calculation Method Settings:

Informations about Reactive energy calculation method is explained in 

below table. The method of active and reactive energy calculation of 

mechanic and electrical counters must be chosen from the table.

Press SET button for 3 sec. (trA Fo menu is displayed.)

Press SET button (TrA Fo Ctr menu is displayed.)

2

Содержание MPR-53CS

Страница 1: ...selected 1 out 1 and 2 out 2 for output device gives alarm Related contact outputs will close and LEDs will be on Total Hours Shows running time of MPR 53CS from the beginning User can not reset this...

Страница 2: ...will be cancelled and previous value will be activated NETWORK ANALYZER MPR 53CS Current Transformer Ratio Setup In this menu current transformer ratio is set There is no in CT 25 models Current tran...

Страница 3: ...s Press ESC button one by one until SAU E SEt yES is displayed When SAU E SEt yES is displayed press SET button If you press ESC button or choose no option instead of yES option by using UP DOWN butto...

Страница 4: ...onditions are set When hoU r ACT on is chosen the run hour keeps working uncondi tionally is active When hoU r ACT 2 is chosen the run hour runs if second digital input is active When hoU r ACT ALL is...

Страница 5: ...tandart MODBUS RTU message is shown below The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one mes...

Страница 6: ...BY USING REPEATER PK 26 Box Connection Diagram 3 Phase neutral 3 Phase without neutral Note For CT 25 models k When CT 25 is used Red cable is connected to k terminal l When CT 25 is used Black cable...

Страница 7: ...e neutral 3 Phase without neutral Note For CT 25 models k When CT 25 is used Red cable is connected to k terminal l When CT 25 is used Black cable is connected to l terminal 3 Phase without neutral cu...

Страница 8: ...Settings Transformer Ctr Current Transformer Ratio 0001 trn Turn number for CT 25 01 Utr Voltage Transformer Ratio 0001 0 CAL Calculation Method 1 Pin 0000 Not Activated RS 485 Adr Address 1 Bau Baud...

Страница 9: ...al in digital inputs It does not run if there is no signal in digital inputs Betriebsstunden Es zeigt die Betriebsstunden Im Gegensatz zu der Gesamtstunden k nnen die Betriebsstunden r ckgestellt und...

Страница 10: ...hlt werden Dr cken Sie auf SET Taste f r 3 Sekunden trA Fo Men ist angezeigt Dr cken Sie auf SET Taste TrA Fo Ctr Men ist angezeigt Sie das CAL CUL At on Men blinkelt Mit AUF oder AB Tasten w hlen Si...

Страница 11: ...n aber sind noch nicht aktiviert F r die Aktivierung der eingegebenen Daten befolgen Sie die folgende Schritten Dr cken Sie auf ESC Taste bis SAU E SEt yES ist angezeigt Dr cken Sie auf SET Taste W hr...

Страница 12: ...oUr ACt 1 ausgew hlt ist funktioniert die Betriebsstunden nur wenn der Digitaleingang 1 aktiv ist Falls hoUr ACt 2 ausgew hlt ist funktioniert die Betriebsstunden nur wenn der Digitaleingang 2 aktiv i...

Страница 13: ...Zeit zwischen 3 5 Zeichen Zeit in denen keine Daten ber die Kommunikations Bus ausgetauscht werden m ssen damit die angeschlossenen Ger te die Ende einer Nachricht und dem Beginn eines anderen zu erk...

Страница 14: ...HLIESSEN PK 26 Kassenanschlussplan 3 Phasen ohne Neutral Anschluss Nur g ltig f r MPR 53S k Wenn CT 25 benutzt ist rotes Kabel ist an der Klemme k angeschlossen l Wenn CT 25 benutzt ist schwarzes Kabe...

Страница 15: ...Kassenanschlussplan 3 Phasen mit Neutral Anschluss 3 Phasen ohne Neutral Anschluss Nur g ltig f r MPR 53S k Wenn CT 25 benutzt ist rotes Kabel ist an der Klemme k angeschlossen l Wenn CT 25 benutzt i...

Страница 16: ...gen Die Nichteinhaltung dieser Anweisungen f hrt zu schweren Verletzungen oder zum Tod Vor der Installation entfernen Sie die Leistungsenergie an den Ger ten Wenn das Ger t an das Netzwerk verbindet i...

Отзывы: