29
UPS Shipping Weight
kg (lb) W/O ISOTR
24 (52.8)
28 (61.6)
Environment
Operating Temperature
0~40
°
C / 32~104
°
F
Storage Temperature
-20~50
°
C / -4~122
°
F
Altitude
2000 meters max
Audible Noise
(1 meter from surface)
60 dBA
< 60 dBA
Relative Humidity
0 ~ 95% humidity, non-condensing
Conformance
Safety
CE
EMC (EMS / EMI)
EN 62040-2, CISPR 22
EN 62040-2
EN 62040-2, CISPR 11
Equipment Protection
Policy
Warranty policy may vary depends on region
Power Dissipation
1433 BTU/h
2389 BTU/h
For RM model at PF0.9
Tower model (with LCD display)
6000VA
10000VA
Capacity
Capacity (VA)
6000VA
10000VA
Capacity (W)
5400W
9000W
Output
Voltage (on battery)
208V, 220V, 230V, 240V +/-2% (Selectable Output Voltage)
Frequency
(on battery)
50 / 60 Hz +/-0.5%
Transfer Time
0 ms
Overload Recovery
Auto transfer to UPS
High Efficiency mode
(AC to AC)
> 95 %
> 97 %
UPS Design Technology
On-Line / Fully digitized microprocessor controlled
Output Wave Form
Sine wave
Harmonic distortion
< 3% of T.H.D. at linear load
Crest Factor
3 : 1
Protection
and
Filtering
Surge Protection
IEC 61000-4-5 level 3
Overload Protection
106
~120% for 30 seconds and
121~150% for 10 seconds
106~120% for 30 seconds and
121~150% for 10 seconds
Short Circuit Protection
UPS output cut off immediately or input fuse / circuit breaker protection
System/
Display/
Warning
Visual Display
(LED model)
UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow),
fault(red)
Visual Display
(LCD model)
Input / output voltage, input / output frequency, on-line mode, back up mode,
battery capacity, load level
Audible Alarm (Battery
back-up)
Beep every 5 sec
UPS Fault
Continuous beeping sound and LCD display
Communication
RS-232 Serial Port and USB
Battery
Type
Sealed, maintenance-free lead acid batteries
DC Voltage (V) Battery
(EBP)
240V / 12V7AH
x 20
240V / 12V9AH
x 20
Typical Recharge Time
to 90% Full
4 hours
Management
Self-test, adjustable battery transfer points and alarm settings
Battery Protection
Cut off without draining any current when battery is low
Cold Start (DC start)
YES
Back Up Time
About 3~5min. Full load /
10~15 min. Half load
About 3~5min. Full load /
9~10 min. Half load
Physical
Input Inlet
Hardwire
Receptacles