22
Settings
LCD
display
Explanation
Selection
Factory
default
Output Volt.Setting
O/P V
Setting
Select Nominal Voltage
208/220/230/240 V
230V
Input/Frequency
I/P F Setting
Select input frequency
range when UPS goes into
free run mode
±2%
±5%
±7%
±5%
Input/Bypass
Voltage
I/P Bypass
Set
Select Input Voltage range
when bypass is available
±10%
+10/-15%
+15/-20%
+10/-15%
Free Run Mode
Free Run
Set
Select if UPS can run in
Free run mode
(unsynchronized)
ON/OFF
ON
Bypass
Enable/Disable at
Free run mode
Bypass
disable
If Enable is chosen, the
UPS can go to bypass when
unsynchronized.
Disable/Enable
Disable
He mode Setting
HE Mode
Set
Select if UPS runs in high
efficiency mode
ON/OFF
OFF
Force Manual
Bypass
Manual
bypass
Permanently force UPS to
bypass. For service only.**
ON/OFF
OFF
Do Battery Test
Battery Test
Detect battery is normal or
not.
Silence Function
Silence Set
Enable or disable silence
function
ON/OFF
OFF
Number of
External battery
Packs
Bat Cabinet
Set
This setting is needed
For UPS to predict
Backup time
0 (only internal batteries)
1(one external cabinet)
2 (two external cabinets)
0
Site wiring alarm
Sit Fault Set
You can enable or disable
the site wiring alarm
Enable /Disable
Disable
Select Language
Language
Select load language
English, German, French,
Spanish, Italian.
English
Set Generator Mode Generator
Set unit in generator mode.
***
ON/OFF
OFF
Set RS232
communication
RS232
Control
Set RS232 communication
enable or disable
Enable/Disable
Enable
Manual test of the UPS
Manual UPS or Manual Battery tests can be conducted from the UPS configuration as well
and are functional even when the UPS is not charging the battery.
Manual Battery test: Scroll the parameters until Manual Bat test displays on the LCD.