8.
Remote Commissioning Parameters
Parameter
Description
Default /
Notes
Rocker Switch Parameters
RockerSwitch-
OnSpeed
Ramp-up speed when rocker
input request light switch ON
20%/s
0= No ramp
(immediate)
RockerSwitch-
OffSpeed
Ramp-down speed when rocker
input request light switch OFF
20%/s
0= No ramp
(immediate)
RockerDim-
UpSpeed
Ramp-up speed when rocker
input request light dim UP
20%/s
0= No ramp
(immediate)
RockerDim-
DownSpeed
Ramp-down speed when rocker
input request light dim DOWN
20%/s
0= No ramp
(immediate)
RockerSwitch-
AutoOffTimer
Delay after last switch action
before light is switched OFF
automatically
0 (disabled)
RockerDimEnable Enables or disables dimming via
rocker switch
ON (enabled)
Scene Pair 1,2
Button 1,2
Defines light levels for scene
buttons
1,25,50,75
Occupancy Sensor Parameters
OccAutoOn
Defines if a signal from an
occupancy sensor automatically
switches on lights (True/False)
FALSE if at least
one switch is
linked,
otherwise TRUE
OccAutoOnLevel
Dimming value at which light is
switched on in case of Auto ON
event from occupancy sensor
100%
OccAutoOnDelay Time before the occupancy sensor
can switch the light back ON in
Auto ON Mode after the user
switched it OFF
15 min
OccAutoOffTime1
Time after which current light level
will be relatively changed by
AutoOffLevel1
10 min
OccAutoOffTime2
Time after which lights will be
switched to AutoOffLevel2
5 min
OccAutoOffLevel1
Factor applied to current light
50%
level if AutoOffTimer1 elapses
Range: 0-200%
OccAutoOffLevel2
Output value to which lights will
be dimmed if AutoOFFtimer2
elapsed
VacancyGrace-
Timer
If occupancy is detected within
the VacancyGraceTimer period
after an occupancy Auto OFF
event, lights are turned back ON
45 s
Field device
Enables and defines the wired
external occupancy sensor input
disabled
Light Level Sensor Parameters
DaylightingMode 2-level or 5 point continuous
daylight dimming
5 point
PhotoOnThres
In case of 2-level mode, light is
switched to MaxVoltageLevel if
light level is below PhotoOnThres
<200lux
PhotoOffThres
In case of 2-level mode, light is
switched to MinVoltageLevel if
light level is above PhotoOffThres
>400lux
LEV1…5
Defines 5 input light levels for
open loop dimming curve
(LEV1<LEV2<...<LEV5)
100, 200, 400,
600, 800 lux
OUT1…5
Defines the LED controller output
values for the corresponding input
light levels
100, 100%, 60%,
20%, 0%
RAMP
Ramp speeds between light levels
1%/s
LlsAdjustment-
Delay
Time before the light level sensor
can adjust the output light level
after it was set by the user
15 min
Generic Sensor Parameters (Occupancy and Light Level)
SensorRamp-
UpSpeed
Ramp-up speed when change is
triggered by an occupancy or light
level sensor (2 point mode)
20%/s
0= No ramp
(immediate)
SensorRamp-
DownSpeed
Ramp-down speed when change
is triggered by an occupancy or
light level sensor (2 point mode)
20%/s
0= No ramp
(immediate)