background image

LEDRU LED 0-10V Zone Controller Installation Guide  

© 2018 EnOcean GmbH    V3.0 

LEDRU-W-EO / LEDRU-W-AU  DD08 and up 

  Page 

 

 

Package Contents 

Tools Required 

 

LED Relay Zone 
Controller

 

 

Screwdriver 

 

Wire nuts

 

 

Product Description 

The LED relay zone controller uses wireless technology to 
communicate with other self-powered EnOcean based 
products and provides an amazingly simple solution for 
dimming control of LED lighting.  

The compact size enables flexible installation inside of or 
next to electrical boxes and fixtures so it can be easily wired 
out of sight using standard wiring practices.  

Simply link the module to an EnOcean-based motion sensor, 
light level sensor or rocker switch and experience levels of 
efficiency and convenience that can only be achieved 
through wireless controls.  

It is also possible to connect a 12V DC powered, wired 
occupancy sensor. 

Product Features Include: 

 

Enables wireless dimming of a single fixture or a zone of 
multiple daisy chained LED fixtures (e.g. 20 each 30W or 
10 each 60W). 

 

Supports California Title 24 daylight harvesting scenarios, 
occupancy control and manual dimming with input from 
self-powered wireless switches and sensors. Implements 
load shedding initiated by separate Demand Response 
controllers 

 

Installs inside or mounts to electrical box using threaded 
connector 

 

Supports wireless remote commissioning to link devices 
and set parameters

 

Specifications (typ. values) 

Power Supply 

120V - 277V VAC, 60 Hz 

Maximum Load 

General Purpose: 16A @ 120/277VAC 

Resistive: 16A @ 120/277VAC 
Tungsten: 960W @ 120VAC 
Ballast / LED Driver: 600W @ 120VAC 

0-10V output 

Tole3%/-4% (1-10V range) 

Current sinking 35mA*, sourcing 20mA 

Power Consumption  1W full load 

0.35W quiescent 

Surge Protection 

3kV line to line, exceeding  

IEC61000-4-5 installation class 4 

Inputs/Outputs 

Flying-lead style wires: 

 

2 power input wires 

 

1 switched output wire 

 

0-10V control output 

 

12V DC external occupancy sensor  

Interface (25mA load max)  
only for 

LEDRU-W-AU

 

Local User Interface  2 Buttons, 1 bi color LED for device    

configuration & manual control 

RF Standard 

EnOcean 902 MHz (LEDRU) 

Transmission Range  100 ft. (30 m) 
Status reporting EEP 

(Outbound EnOcean 
Equipment Profile)  

D2-40-00 (default) 
A5-11-01 (alternate) 
A5-38-08 (Master / Gateway)  

RECOM 

V1.1 - Compatible with Navigan™ 

Interoperable 

Products / EEPs 
(Inbound EnOcean 
Equipment Profiles) 

 

Rocker Pad Switch (F6-02-02) 

Occupancy Sensor  

(A5-07-01, A5-07-02, A5-07-03) 

Light Level Sensor  

(A5-06-02, A6-06-03) 

Central Controller (A5-38-08) 
Demand Response (A5-37-01) 

Dimensions 

2.78” H x 1.65” W x 1.1” D  

(73mm x 42mm x 28mm) 

Weight 

3.2oz. (90g) 

Mounting 

 

Connect to electrical boxes and   
fixtures using threaded nipple 

 

Install inside standard electrical box 

Environment 

 

Indoor use only 

 

32° to 140° F (0° to 60° C) 

 

20% to 85% relative 
humidity  (non-condensing) 

Agency Compliance  UL244A, UL 1472, CSA/CAN 

C22.2 No. 184.1, FCC, IC 

UL2043 Plenum Rated 

Содержание LEDRU

Страница 1: ...wireless remote commissioning to link devices and set parameters Specifications typ values Power Supply 120V 277V VAC 60 Hz Maximum Load General Purpose 16A 120 277VAC Resistive 16A 120 277VAC Tungsten 960W 120VAC Ballast LED Driver 600W 120VAC 0 10V output Tolerances 3 4 1 10V range Current sinking 35mA sourcing 20mA Power Consumption 1W full load 0 35W quiescent Surge Protection 3kV line to line...

Страница 2: ...which of the two installation methods is most appropriate A Installed inside the electrical box NOTE For best performance remove the antenna from its slot and elongate it outside and away from the box B Installed using the threaded connector i Insert the threaded connector through a diameter knockout ii Thread the 5 module wires inside the electrical box and through the lock nut 4 Connect the wire...

Страница 3: ...es Transmitters switches and sensors can provide input data to the LED controller Transceivers Gateways or controllers can exchange data and commands with the LED controller An LED controller is also capable of controlling other LED controllers in a Master Slave scenario To establish links the LED controller must be powered and within wireless range of the device it is to be linked with Inbound li...

Страница 4: ...D starts toggling indicating that linking unlinking mode is active The connected load will toggle between 10 and 90 2 Shortly press the DIM button This will cause the LED Controller to transmit a link message teach in message identifying the status message EEP used by it 3 Press the LRN button again for 1 second or wait 30 seconds to return to normal operation Setting the minimum output voltage le...

Страница 5: ...od defined by RockerSwitchAutoOffTimer This feature can be disabled by setting RockerSwitchAutoOffTimer 0 This feature is automatically disabled if an occupancy sensor is present In this case automatic switch OFF of the light will be performed based on the input from the occupancy sensor as described below Occupancy Sensors only Auto Off Timers If at least one sensor detects motion Light level is ...

Страница 6: ... DaylightingMode to 2 level mode via remote commissioning The thresholds for switching between the two levels are defined by PhotoOnThres and PhotoOffThres Repeater function The LED controller provides the option to activate one level repeat only original telegrams or two level repeat original telegrams or telegrams that were repeated once repeater mode for EnOcean radio telegrams By default Repea...

Страница 7: ...an switch the light back ON in Auto ON Mode after the user switched it OFF 15 min OccAutoOffTime1 Time after which current light level will be relatively changed by AutoOffLevel1 10 min OccAutoOffTime2 Time after which lights will be switched to AutoOffLevel2 5 min OccAutoOffLevel1 Factor applied to current light 50 level if AutoOffTimer1 elapses Range 0 200 OccAutoOffLevel2 Output value to which ...

Страница 8: ...rn telegram from a linked device is received while in operating mode the 0 10V output will toggle once between 10 and 90 ON enabled Switch diming curve Defines four different diming curved Linear curve Enable relay on permanently Relay out line voltage will not be cut off if enabled Disabled Accumulated uptime value Accumulated time for output On n a Average output value Average output dim level o...

Отзывы: