Repeater-EnO868SELV
EnOcean Repeater 868 MHz
Repeater-EnO868USB
Read the operating instructions carefully before commissioning.
Installation and operating instructions
Rev.: February 2016
Repeater-EnO868_104126_OperationManual_E_FEB2016.doc/pdf
Page 4 of 7
BootUp GmbH
|
Sonnenbergstrasse 23
|
CH-5236 Remigen
|
Switzerland
|
Phone +41 56 284 09 21
|
Fax +41 56 284 09 22
2016
|
Omi technical changes excepted
|
www.BootUp.ch
|
www.myHomeControl.ch
|
Power supply
If a different power supply is used, it should be noted that this may affect the function of the device.
USB power adapter
(supplied with RepeaterEnO868USB)
The device with the USB plug can be connected directly to the USB power adapter. This is a plug and play
solution and can be run by the layman. This complete system consisting of the repeater and the USB wide-
range power supply 230V AC 5V DC, 0.7A has been tested (CE relevant measurements).
Electronic short circuit and overload protection
Input voltage: 110V ... 230V AC
Output voltage: 5V DC; maximum 0.7A
Black. Euro plug
Ordering Information:
Model / Type
Description
Article No.
USB Power Supply EC
USB Power Supply 230V AC 5V DC, 0.7A
001.915
SELV 6V DC
(not included in the delivery)
The repeater is supplied via low voltage 6V DC. This whole system
consisting of the repeater and the UP6 wide range power supply 100-240V AC, 6V DC,
SELV power supply has been tested (CE relevant measurements).
Input voltage: 100 to 240 V AC (+- 10%), 150 mA, 50 to 60 Hz
Output voltage: 6V DC, 1000mA, ripple 300 mVpp, current limited, sustained short-circuit proof, standby <0.3W.
Standards: Fulfils Class II SELV for the following applications: EN 60950 / IEC 60950, UL 60950, VDE, CE
EMC: Conforms to EN 55011, 55014, EN 55022 / B, EN 55024, FCC 41 part 15, EN 61000-3-2, EN 61000-4-2,
EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-11,
Dimensions: 51 x 48 x 35 mm, 95 g, IP 64
Bestellinformationen:
Model / Type
Description
Article No.
UP6
Flush mounting wide range power supply 100-240V AC,
6V DC 1000mA; SELV
001.900
To operate the USB Repeater with the UP6 power supply
1. Cut off the USB cable with the plug and shorten as per installation, then stripping
2. Cut off the following wires: Shield, green, white and isolate the shield
3. Connect to the UP6 power supply, repeater ground (black) on UP6 black, re UB (red) on UP6 red.
Radio ranges between senders and receivers
The signal strength of the radio signals decreases as the distance between transmitter and receiver increases.
In buildings, the range of the radio signals depends on the building materials used there. In addition, the angle
plays a role with which the signal sent hits the wall. Depending on the angle changes the effective wall thickness
and thus the attenuation of the signal. If possible, the signals should run vertically through the masonry. Wall
niches are to be avoided.
Material typical ranges:
Sight connection
30m in corridors and up to 100m in halls
Masonry
20m, by maximal 3 walls
Reinforced concrete 10m, by maximal 1 wall / ceiling
Plasterboard / wood 30m, by maximal 5 walls