
Page 2
Page 3
Page 4
Tile Mount Sensor Installation
Figure 2
Fixture Mount Sensor Installation
Caution
Installation and maintenance must be performed by a qualified
electrician in accordance with local, state, and national electrical
codes (NEC) and requirements.
Spring Arms
Figure 4
Figure 3
LED Status
Description/Solution
LED not on
Check power and wiring
Purple solid
All LEDs are on during boot time for 5-6 seconds
Green blinking
Sensor commissioned and working
Red blinking
Incompatibility between LED driver and sensor
– Replace LED driver and if not resolved,
replace sensor.
Red solid
Faulty sensor – replace sensor
Green solid
Sensor installed, initialized, and
uncommissioned
–
waiting for discovery.
Blue solid
Image being upgraded.
LED Description
Step 1: Switch off the circuit breaker supplying power to the
light.
Step 2
:
Mount the Control Unit (CU) behind the ceiling tile or in
a UL approved enclosure. Refer to the
Control Unit Installation
Guide
.
Step 3
:
Connect the RJ-12 connector end of the Compact
Sensor cable to the Control Unit. See Figure 1. For a detailed
wiring diagram, see Figure 6.
Note: The sensor is designed to
mount in a 15/16
th
inch hole in
the ceiling tile.
Step 4: Make a small circular cut
in the ceiling tile.
Step 5
:
Pull the other 6-pin end of
the Compact Sensor cable
through the hole in the tile.
Figure 1
Step 6: Insert the end of the wire into the sensor’s 6-pin
connector. See Figure 2.
Step 7
:
Push the spring arms together and insert the sensor
through the hole in the tile. See Figure 2.
Step 8: Turn the power on by switching on the circuit
breaker.
Step 1
:
Switch off the circuit breaker supplying power to the
light.
Step 2
:
Mount the Control Unit (CU) in the ballast cavity of
the fixture or in a UL approved enclosure. Refer to the
Control Unit Installation Guide
.
Step 3
:
Connect the RJ-12 connector end of the Compact
Sensor cable to the Control Unit. See Figure 1. For a detailed
wiring diagram, see Figure 6.
Step 5
:
Unthread the spring arms
from the Compact Sensor. See
Figure 4.
Step 8: Turn the power on by switching
on the circuit breaker
.
Step 6: Insert the Compact Sensor
through the hole in the fixture. Use the
spring arms from behind the sensor to
fasten the Compact Sensor.
See Figure 5.
Step 7
:
Insert the 6-pin end of the
Compact Sensor cable to the 6-pin
connector on the sensor. See Figure 5.
Step 4
:
Determine the
location for the sensor in the
fixture and cut a
½
inch
knockout in the fixture. See
Figure 3.
Figure 5
Figure 6
Compact
Sensor Cable
Note: The sensor is
designed to mount in a
½
inch trade size knockout on
a fixture.