FAULTY CIRCUIT BOARD:
The circuit board has a Green power LED and 3 function LED’s.
When any of the 3 output LED’s are illuminated 24VAC is supplied to the
corresponding ¼” Spade terminal on the board.
If the Green power LED is not illuminated check that the board fuse is not
blown and replace if necessary.
If there is malfunction a temporary circuit board bypassed can be utilized
until a replacement circuit board is installed.
With the power off
-
remove the fuse from the circuit board
-
Move the “PUMP” wire (Orange/Black stripe) and the “High
Fan” wire (White/Red Stripe) to the two extra W terminals.
This will allow the pump and blower to run with a call for heat
from the thermostat.