PUMP CONTROL:
LOW VOLTAGE CONTROL BOARD
During the heating season the pump is controlled by the low voltage
circuit control board.
The control board also operates as an off season pump circulator to
eliminate stagnant water in the heat exchanger. This pump cycle will
operate for 1 minute every 12 hours after the last call for heat.
SEQUENCE OF OPERATION IN HEATING MODE:
1.
When the thermostat calls for heat (W) the pump and blower motor
will run at the selected operating fan speed.
2.
When the thermostat ends the call for heat (W) the pump and
blower turn off. The blower will continue running at the
continuous low speed if the thermostat is set to FAN-ON.
Note: Upon powering up
the air handler circuit
board starts a 15 second
initialization during which
the pump operates for 5
seconds.
Circuit board LED
illuminates when the
pump is operating during
heating and pump purge
cycles.