ELECTRIC EQUIPMENT

OIL BURNER CONTROL: LOA21... / LOA24...

FUNCTION

1.

Switch on operating switch and twin thermostat
The burner motor starts, an ignition spark is formed, the prepurge goes
on till the prepurge period expires and the solenoid valve opens (2).

2.

Solenoid valve opens
Oil mist is formed and ignited. The photocell indicates a flame.

(1)

The ignition spark goes out 15 s. after flame indication 

(LOA24.171...)

.

(2)

The ignition spark goes out 2 s. after flame indication when the ignition
transformer is connected to terminal 7

 (LOA24.173...)

.

3.

The safety time expires
a. If no flame is established before this time limit the control cuts out.
b. If for some reasons the flame disappears after this time limit, the

burner will make an attempt to re-start.

3-4.

Operating position
If the burner operation is interrupted by means of the main switch or the
thermostat, a new start takes place when the conditions in accordance
with point 1 are fulfilled.

The oil burner control cuts out
A red lamp in the control is lit. Press the reset button and the burner
re-starts.

Post-ignition

(2)

If a post-ignition of 15 s. is wanted, move the ignition transformer from
terminal 7 to terminal 6 

(LOA24.173...)

.

LIST OF COMPONENTS

A1 Oil burner control

P1 Time meter (optional)

A2 Twin thermostat

R1 Photoresistor

F1 Fuse, max. 10A

S3 Main switch

H1 Alarm lamp

T1 Ignition transformer

H2 Signal lamp (optional)

Y1 Solenoid valve

M1 Burner motor

Mains connection and fuses in accordance with local regulations.

TECHNICAL DATA

Pre-ignition time:

13  s

Pre-purge time:

13  s

(1)

 Post-ignition time:

15 s

(2)

 Post-ignition time:

2 s

Safety lock-out time:

10 s

Reset time after lockout:

≈ 

50 s

Reaction time on flame failure:

max.  1  s

Ambient temperature:

from - 20 to +60°C

Min. current with flame established:

65   A

Max. photo current at start:

5   A

Enclosure:

IP 40

(Under voltage proof only LOA24...)

CONTROL OF PHOTO CURRENT

Current through photo unit is measured with a d.c. ammeter (a moving coil
instrument connected in series with the photo unit).

171 415 16  04-01

WIRING DIAGRAM

(1)(2)

Содержание Bentone B 30A CN

Страница 1: ...Providing sustainable energy solutions worldwide 178 024 51 Installation and maintenance instruction B 30A CN...

Страница 2: ......

Страница 3: ...ionelectrodes 4 Nozzle assembly 5 Ignitioncable 6 Ignitiontransformer 7 Controlbox 8 Reset button 9 Cover inspectionglass 10 Fanwheel 11 Motor 12 Photo cell 13 Nozzle assembly adjustment 14 Blast tube...

Страница 4: ...MENSIONS OUTPUTRANGEANDNOZZLESRECOMMENDED RECOMMENDEDNOZZLE Because of different boiler types existing on the market with varying combustionchamberdesigns itisnot possibletostateadefinitesprayangle or...

Страница 5: ...ncrease the nozzle assembly adjustment somewhat The CO2 con tent and consequently the air volume will then be reduced CONDENSATIONINCHIMNEY A modern burner works with less ex cess air and often also w...

Страница 6: ...r at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipes by loosening screw A SERVICE OF BURNER HEAD 171 305 74 95 01 1 Loosen or swing out the burner from th...

Страница 7: ...ordance with point 1 are fulfilled The oil burner control cuts out A red lamp in the control is lit Press the reset button and the burner re starts Post ignition 2 If a post ignition of 15 s is wanted...

Страница 8: ...suction line tables consist of theoretically calculated values where the pipe dimensions and oil velocity havebeenmatchedsothatturbulences will not occur Such turbulences will resultinincreasedpressu...

Страница 9: ...nto startingposition This can be remedied by Reducing the pump pressure Reducing the oil quantity supplied by using a smaller nozzle Usingapumpwithalargercapacity Thediaphragmandthespringkeep the pump...

Страница 10: ...79 7 97 94 81 2 00 6 65 79 68 7 06 84 72 7 45 88 76 7 81 93 80 8 18 97 83 8 49 101 86 8 81 104 90 9 12 108 93 2 25 7 49 89 76 7 94 94 81 8 38 99 85 8 78 104 89 9 18 109 94 9 55 113 97 9 91 117 101 10...

Страница 11: ...as not reset Appliance overheat device has operated Control relay or photocell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue...

Страница 12: ...nt conformes aux normes et aux documents normatifs suivants et satisfont aux crit res applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direktiven CE suivan...

Страница 13: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...