DELAYED IGNITION, BURNERS STARTS VIOLENTLY

BURNER FAILS TO START AFTER NORMAL OPERATION

Remedies

Situation

Possible causes

BURNER FAILS TO START

Check ignition transformer. Check electrode

gap and porcelain

Reset overheat device. Find reason for its

operation and rectify

Check or replace fuse if necessary. Check

reason for failure

Check operation of magnetic valve

Check that photocell is not seeing ambient light

Motor runs

Flame instability

Burner pre-purges

Burner locks out

Motor runs

Photocell failed

Control faulty

Confirm with new photocell

Confirm with new control. (NB. it is advisable to

change the photocell if also changing control)

Burner pre-purges

Burner locks out

No oil

Check that H.T. leads are sound and are not

arcing other than at electrode gap

No flame occurs

Check oil supply to burner - check that pump

is not airlocked

Burner fails to start

Lamp not lit

Fuse has blown

Appliance thermostat has not reset

Appliance overheat device has operated

Control relay or photocell defective

Adjust thermostat

Check by replacement

Motor runs

Burner runs to lockout

No oil being delivered

Excessive flue draught is preventing

flame establishment

No spark

Check that tank, oil lines, fire valve, pump and

nozzle are all in good order

Rectify condition

Excessive draught

Adjust the burner

Burner pulsates on start-up

Nozzle partly blocked

Oil pressure too low

Flue blocked or damaged

Fan slipping on shaft

Pump coupling loose or worn

Replace nozzle

Check and adjust

Check and rectify

Check and retighten

Delayed ignition

Check the electrode adjustment, see diagram

Check electrodes for damage

Check H.T. leads for damage and disconnection

Check and replace

Incorrect head settings

Low oil pressure

Photocell not seeing light

Excess air

Burner pulsates on start-up

only with hot flue

Burner starts violently

False light

No spark

Check oil pressure

Check that photocell is clean and unobstructed

Check nozzle to burner head dimension and

electrode position

Adjust air damper

Flame occurs

171 915 01  08-01

FAULT LOCATION

Содержание Bentone B 30A CN

Страница 1: ...Providing sustainable energy solutions worldwide 178 024 51 Installation and maintenance instruction B 30A CN...

Страница 2: ......

Страница 3: ...ionelectrodes 4 Nozzle assembly 5 Ignitioncable 6 Ignitiontransformer 7 Controlbox 8 Reset button 9 Cover inspectionglass 10 Fanwheel 11 Motor 12 Photo cell 13 Nozzle assembly adjustment 14 Blast tube...

Страница 4: ...MENSIONS OUTPUTRANGEANDNOZZLESRECOMMENDED RECOMMENDEDNOZZLE Because of different boiler types existing on the market with varying combustionchamberdesigns itisnot possibletostateadefinitesprayangle or...

Страница 5: ...ncrease the nozzle assembly adjustment somewhat The CO2 con tent and consequently the air volume will then be reduced CONDENSATIONINCHIMNEY A modern burner works with less ex cess air and often also w...

Страница 6: ...r at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipes by loosening screw A SERVICE OF BURNER HEAD 171 305 74 95 01 1 Loosen or swing out the burner from th...

Страница 7: ...ordance with point 1 are fulfilled The oil burner control cuts out A red lamp in the control is lit Press the reset button and the burner re starts Post ignition 2 If a post ignition of 15 s is wanted...

Страница 8: ...suction line tables consist of theoretically calculated values where the pipe dimensions and oil velocity havebeenmatchedsothatturbulences will not occur Such turbulences will resultinincreasedpressu...

Страница 9: ...nto startingposition This can be remedied by Reducing the pump pressure Reducing the oil quantity supplied by using a smaller nozzle Usingapumpwithalargercapacity Thediaphragmandthespringkeep the pump...

Страница 10: ...79 7 97 94 81 2 00 6 65 79 68 7 06 84 72 7 45 88 76 7 81 93 80 8 18 97 83 8 49 101 86 8 81 104 90 9 12 108 93 2 25 7 49 89 76 7 94 94 81 8 38 99 85 8 78 104 89 9 18 109 94 9 55 113 97 9 91 117 101 10...

Страница 11: ...as not reset Appliance overheat device has operated Control relay or photocell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue...

Страница 12: ...nt conformes aux normes et aux documents normatifs suivants et satisfont aux crit res applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direktiven CE suivan...

Страница 13: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Страница 14: ......

Страница 15: ......

Страница 16: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: