GENERAL INSTRUCTIONS

GENERAL RULES

The installation of an oil burner should
be carried out in accordance with local
regulations. The installer of the burner
must therefore be aware of all
regulations relating to oil and combu-
stion.
Only oil suitable for the burner should
be used and then in combination with
a suitable oil filter before the oil pump
of the burner.
If the burner is replacing an existing
burner make sure that the oil filter is
replaced or cleaned. The installation
must only be undertaken by experien-
ced personnel. Care should be taken
by the installer to ensure that no
electrical cables or fuel/gas pipes are
trapped or damaged during installation
or service/maintenance.

INSTALLATION INSTRUCTIONS

General installation instructions ac-
company the burner and should be left
in a prominent place adjacent to the
burner.

ADJUSTMENT OF BURNER

The burner is from the factory pre-set to
an average value that must then be
adjusted to the boiler in question.
All burner adjustments must be made
in accordance with boiler manufacturers
instructions.These must include the
checking of flue gas temperatures,
average water temperature and CO

2

 or

O

2

 concentration.

To adjust the combustion device, start
by increasing the air volume and the
nozzle assembly somewhat.When the
burner starts it is  burning with excess
air and smoke number 0. Reduce the
nozzle assembly adjustment until soot
occurs, and then increase the
adjustment to make the soot disappear
again. Then the volume of air is reduced
until soot occurs and increased again
to reach a combustion free of soot.
By this procedure an optimum adjust-
ment is obtained. If larger nozzles are
used the preadjustment of both the air
volume and the nozzle assembly must
be increased.
A whistling sound may be heard which
can be eliminated or reduced as fol-
lows: Increase the nozzle assembly
adjustment somewhat. The CO

2

-con-

tent and consequently the air volume
will then be reduced.

CONDENSATION IN CHIMNEY

A modern burner works with less ex-
cess air and often also with smaller
nozzles than older models.

This increases the efficiency but also
the risk of condensation in the chimney.
The risk increases if the area of the
chimney flue is too large. The tempera-
ture of the flue gases should exceed
60°C measured 0,5 metres from the
chimney top.
Measures to raise the temperature:
Insulate the chimney in cold attics
Install a tube in the chimney
Install a draught regulator (dilutes the
flue gases during operation and dries
them up during standstill)
Increase the oil quantity
Raise the flue gas temperature by
removing turbulators, if any, in the
boiler.

PUMP ADJUSTMENT

See separate description.

171 305 46  06-01

B

ADJUSTMENT OF NOZZLE
ASSEMBLY

Loosen the screw G and adjust the
nozzle assembly by turning the screw
F.

Max. capacity

- Front position

Medium capacity - Middle position
Min. capacity

- Rear position

AIR ADJUSTMENT

Loosen the stop screw B and turn the
knob along the scale to the position
wanted  and tighten the screw. Check
the air adjustment by making a flue gas
analysis.

MAINTENANCE

The boiler/burner should be examined
regularly for any signs of malfunction
or oil leakage.

OIL SUPPLY

The oil line should be dimensioned in
accordance with the pump manu-
facturer´s instruction. In the suction
line to the burner a filter should be
mounted to prevent any particles in the
oil from reaching the burner. If the
installation consists of several burners
each one should have its own suction
line from the tank or a circulation sy-
stem should be used.
The temperature in the oil line should
be kept as constant as possible. Avoid
exposing the line to excessive cold
which may cause blockages of paraffin
deposits.
The oil pipe and electric cable should
be fitted so that the burner can be
placed on the floor for inspection of the
combustion device.

G

F

Содержание Bentone B 30A CN

Страница 1: ...Providing sustainable energy solutions worldwide 178 024 51 Installation and maintenance instruction B 30A CN...

Страница 2: ......

Страница 3: ...ionelectrodes 4 Nozzle assembly 5 Ignitioncable 6 Ignitiontransformer 7 Controlbox 8 Reset button 9 Cover inspectionglass 10 Fanwheel 11 Motor 12 Photo cell 13 Nozzle assembly adjustment 14 Blast tube...

Страница 4: ...MENSIONS OUTPUTRANGEANDNOZZLESRECOMMENDED RECOMMENDEDNOZZLE Because of different boiler types existing on the market with varying combustionchamberdesigns itisnot possibletostateadefinitesprayangle or...

Страница 5: ...ncrease the nozzle assembly adjustment somewhat The CO2 con tent and consequently the air volume will then be reduced CONDENSATIONINCHIMNEY A modern burner works with less ex cess air and often also w...

Страница 6: ...r at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipes by loosening screw A SERVICE OF BURNER HEAD 171 305 74 95 01 1 Loosen or swing out the burner from th...

Страница 7: ...ordance with point 1 are fulfilled The oil burner control cuts out A red lamp in the control is lit Press the reset button and the burner re starts Post ignition 2 If a post ignition of 15 s is wanted...

Страница 8: ...suction line tables consist of theoretically calculated values where the pipe dimensions and oil velocity havebeenmatchedsothatturbulences will not occur Such turbulences will resultinincreasedpressu...

Страница 9: ...nto startingposition This can be remedied by Reducing the pump pressure Reducing the oil quantity supplied by using a smaller nozzle Usingapumpwithalargercapacity Thediaphragmandthespringkeep the pump...

Страница 10: ...79 7 97 94 81 2 00 6 65 79 68 7 06 84 72 7 45 88 76 7 81 93 80 8 18 97 83 8 49 101 86 8 81 104 90 9 12 108 93 2 25 7 49 89 76 7 94 94 81 8 38 99 85 8 78 104 89 9 18 109 94 9 55 113 97 9 91 117 101 10...

Страница 11: ...as not reset Appliance overheat device has operated Control relay or photocell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue...

Страница 12: ...nt conformes aux normes et aux documents normatifs suivants et satisfont aux crit res applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direktiven CE suivan...

Страница 13: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Страница 14: ......

Страница 15: ......

Страница 16: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Отзывы: