0170022-J0 Rev A
Page 73
9.3.2
FXM HP - Default Values
When a FXM HP system is created, all user configurable parameters are set to their default values.
Table 16:
FXM HP - Default Values (Sheet 1 of 4)
Parameters
Default Settings
System Type
Normal UPS
Battery Float Voltage
54.0V (48V) / 27V (24V)
AC Input Frequency
Auto Detect
AC Input Qualification Time
3 seconds
AC Input Sense
Normal
Automatic Voltage Regulation
Enabled
AC Input High Limit (AVR Disabled)
132V (120V) / 253V (230V)
AC Input Low Limit (AVR Disabled)
108V (120V) / 207V (230V)
Battery Capacity Rating
100Ah
Battery Open Circuit Voltage
51.4V (48V) / 25.7V (24V)
Battery Peukert Exponent
1.00
Battery Runtime Low Alarm
60 minutes
Battery Health Low Alarm
70%
Battery Temperature High Alarm (°C)
75
Battery Temperature Low Alarm (°C)
-20
Charging Current Limit Amps
15A (1100/2000), 10A (650)
Elevated Absorption Charging
Enabled
Elevated Absorption Arming Threshold
48V (48V) / 24V (24V)
Elevated Absorption Voltage
55V (48V) / 27.5V (24V)
Elevated Absorption Termination Threshold
5A
Elevated Absorption Timeout
1.0Hr
Temperature Compensation Slope (mV/°C/Cell)
-2.5
Содержание Alpha FXM HP 1100
Страница 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Страница 2: ......
Страница 4: ......
Страница 12: ...viii...
Страница 28: ...0170022 J0 Rev A Page 16...
Страница 30: ...0170022 J0 Rev A Page 18...
Страница 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Страница 144: ...0170022 J0 Rev A Page 132...
Страница 146: ...0170022 J0 Rev A Page 134...
Страница 148: ......
Страница 149: ......