0170022-J0 Rev A
Page 95
10.2.5
Creating User Alarms
The controller has a set of default standard alarms that are associated with a system or an inventory
item such as a load or a disconnect. These standard alarms may be enough to support many system
configurations. It is also common to need additional alarms, based on the status of the digital inputs or
on the threshold of an analog value read from the input of an ADIO device.
You can create any number of digital or threshold alarms. These alarms have the same behavior as
standard alarms such as alarm cut-off, SNMP traps, and relay mapping. These user-defined alarms can
be created and removed via the
Controller > Advanced Functions > User Alarms
menu.
To create a user alarm:
1. Go to
Controller > Advanced Functions > User Alarms
.
2. Select the type of user alarm to create. A new row for the user alarm will display in the table.
•
If you want to create a digital alarm click the
Add Digital User Alarm
button.
•
If you want to create a high or low threshold alarm click the
Add Threshold User Alarm
button.
3. Click the details icon. Two tables display. One table shows the fields to configure that are specific
to the selected user alarm. The other table shows the standard alarm configuration.
4. Give the alarm a descriptive name. This is important since the same type of user alarms have the
same default name. The alarm description is optional.
5. Select the alarm input source. There are different options depending on the type of user alarm
you are creating.
•
A threshold alarm allows you select from ADIO voltage and temperature inputs, current read
-
ings from shunts or DCCTs and any status count data about rectifiers or converters.
•
A digital alarm allows you to select digital inputs on any ADIO devices.
6. Set the priority and relay. If you want to set a severity value for the SNMP trap, use the Parameter
1 field.
7. If you are configuring a digital alarm, this is all that is required. If you are configuring a threshold
alarm, continue as described below.
Low Battery Warning 2
Major
The battery capacity is below the Low Battery Threshold.
Missing FXM
Critical
The FXM hardware module is missing.
On Battery
Warning
The battery is providing power to the load.
Alarm
Priority
Alarm Description
Содержание Alpha FXM HP 1100
Страница 1: ...Alpha FXM HP 650 1100 2000 UPS Technical Guide 0170022 J0 Effective 11 2019...
Страница 2: ......
Страница 4: ......
Страница 12: ...viii...
Страница 28: ...0170022 J0 Rev A Page 16...
Страница 30: ...0170022 J0 Rev A Page 18...
Страница 142: ...0170022 J0 Rev A Page 130 Figure 70 Upgrade Succeeded...
Страница 144: ...0170022 J0 Rev A Page 132...
Страница 146: ...0170022 J0 Rev A Page 134...
Страница 148: ......
Страница 149: ......