9400016-J0 Rev E
46
User Guide
CXPS-E3
8.9.1 Factory ranges and defaults
Table K lists the rectifier settings, ranges, and defaults. Changes are made through the controller interface.
Table K —
Rectifier factory ranges and defaults
Setting
Range (minimum to maximum)
Default
Float (FL) voltage
47.5V – 58.2V
54V
Equalize (EQ) voltage
49.8V – 60.2V
55V
Battery test (BT) voltage
44V – 52V
46V
Over voltage protection (OVP)*
63V
63V
Current limit (CL)
23% – 100%
100%
Power limit (PL)
0% – 100%
100%
Module start delay
0s – 250s
1s
System start delay
0s – 600s
0s
Low voltage alarm (LVA)
42V – 52V
44V
High voltage alarm (HVA)
52V – 63V
55.5V
EQ timeout
1h – 2399h
30h
BT timeout
1h – 250h
8h
Softstart ramp-rate
Normal/Fast
Normal
CL/PL alarm
Enable/Disable
Enable
Remote shutdown
Enable/Disable
Enable
Ramp test
Enable/Disable
Enable
*The OVP cannot be set below the present system/FL/EQ/BT voltage setting or the safe mode voltage of 51.4V.