7. PROBE CHART
The equipment temperature probes are NTC 10 K
Ω
type, the resistance probe in function of the tempera-
ture is given by the following graphic:
8. TABLE OF ERRORS
The installation, assembly and repair of the equipment can only be carried out by qualified technicians.
Code
Description
Problem / Checking
AL
Very cold temperature in the thermal accu-
mulator (T_water < 5°C).
Equipment keeps the regular function.
AH
Very high temperature in the thermal accu-
mulator (T_water > 80°C).
Equipment keeps the regular function.
Security thermostat turns off the equipment
(rearming the thermostat is handmade)
Pr1
Water temperature probe in the thermal ac-
cumulator damaged.
Solution:
•
Verify the integrity of the probe’s con-
nections on the controller;
•
Measure probe’s resistance (NTC
10K
Ω
, resistance at 25°C equals ±
10K
Ω
);
•
Substitute the probe;
Equipment continues regular function.
Pr2
Water temperature probe in the thermal ac-
cumulator damaged;
Solution:
•
Verify the integrity of the probe’s con-
nections on the controller;
•
Measure probe’s resistance (NTC
10K
Ω
, resistance at 25°C equals ±
10K
Ω
);
•
Substitute the probe;
All the active outputs actives are deactivat-
ed (compressor, resistance and ventilator)
Technical Manual
Содержание MONOBLOC 100esm
Страница 2: ......
Страница 4: ...4 MONOBLOC 100L Manual T cnico Portugu s...
Страница 30: ...30 MONOBLOC 100L Manual T cnico...
Страница 32: ...32 MONOBLOC 100L English Technical Manual...
Страница 58: ...58 MONOBLOC 100L...
Страница 60: ...60 MONOBLOC 100L Espa ol Manual T cnico...
Страница 86: ...Notas Notes Notas...
Страница 87: ...Notas Notes Notas...
Страница 88: ...Notas Notes Notas...
Страница 89: ...Notas Notes Notas...
Страница 90: ...Notas Notes Notas...
Страница 91: ......