5. Configuring the Thermostat Settings
In order to configure the Thermostat to match your HVAC configuration, you must use the
SETUP menu.
1.
Press the Menu/Select (checkmark) button to enter the menu
2.
Scroll down to the SETUP menu
3.
Enter the Install Password “INST”
This will give you access to the additional menu items listed below.
Equipment Type
•
TYPE:
o
Select the type of equipment (conventional or heat pump), the default is
Conventional.
•
# OF COOL STAGES:
o
Select the number of cool stages from 0 to 2, the default is 1.
•
# OF HEAT STAGES:
o
Select the number of heat stages from 0 to 2 (3 for heat pumps), the default is 1.
•
REV. VALVE (for heat pumps only):
o
Select whether the reversing valve is on in cool or on in heat. The default is on in
cool.
Equipment Settings
•
MIN ON/OFF TIME:
o
Select the minimum on/off time from 1 to 6 minutes, the default is 3.
o
A minimum of 2 minutes is recommended for a furnace and 3 minutes for Heat
Pumps and Air Conditioners.
•
FAN ON IN HEAT (for conventional equipment only):
o
Set to yes if the thermostat controls the fan (common in electric furnaces) and no
if the furnace controls the fan (common in gas furnaces). The default is Yes.
•
ALLOW HP+AUX ON (for heat pumps only):
o
Set to yes if the heat pump and auxiliary heat can be on at the same time fan
(common with auxiliary electric heat).
o
Set to no if the heat pump should be off when the auxiliary heat is on (common
with auxiliary fossil fuel heat).
o
The default is Yes.
•
BALANCE POINTS (Only for heat pumps with outdoor temperature sensor):
o
HIGH: Set to the temperature above which the auxiliary heat is disabled. The
range is from -38 °F (-39 °C) to 122 °F (50 °C) and the default is 122 °F (50 °C)
and a typical value is 50 °F (10 °C).
o
LOW: Set to the temperature below which the heat pump is disabled. The range
is from -40 °F (-40 °C) to 120 °F (49 °C) and the default is -40 °F (-40 °C) and a
typical value is 32 °F (0 °C).