6.7 Heat Pump - Two stage with auxiliary stage
Equipment Wiring
Thermostat Settings
Equipment Type
•
TYPE: Heat Pump
•
# OF COOL STAGES: 1
•
# OF HEAT STAGES: 2
•
REV. VALVE:
o
Select whether the reversing valve is on in cool or on in heat. The default is on in
cool.
Equipment Settings
•
ALLOW HP+AUX ON:
o
Set to yes if the heat pump and auxiliary heat can be on at the same time fan
(common with auxiliary electric heat).
o
Set to no if the heat pump should be off when the auxiliary heat is on (common
with auxiliary fossil fuel heat).
o
The default is Yes.
•
BALANCE POINTS (Only for heat pumps with outdoor temperature sensor):
o
HIGH: Set to the temperature above which the auxiliary heat is disabled. The
range is from -38 °F (-39 °C) to 122 °F (50 °C) and the default is 122 °F (50 °C)
and a typical value is 50 °F (10 °C).
o
LOW: Set to the temperature below which the heat pump is disabled. The range
is from -40 °F (-40 °C) to 120 °F (49 °C) and the default is -40 °F (-40 °C) and a
typical value is 32 °F (0 °C).