Enerdrive ePRO Inverter / Charger Owners Manual
Page 12
Description
Enables or disables ASB. If enabled, the inverter will jump to ASB mode
automatically, when the connected load power consumption drops
below a user programmable level. In ASB mode the inverter pulses it’s
output sinewave in order to detect when the connected load requires
more power again. While running in ASB mode, the ePRO Combi itself
draws signi
fi
cantly less current from the battery. As soon as the load
power demand increases again, the inverter will automatically jump
to continuous mode delivering uninterrupted power to the load. When
disabled, the inverter will always run in continuous mode, which is
better for critical loads like computers, clocks and AV equipment.
Con
fi
gurable by
DIP switch (DIP 4) and Dashboard
Parameter
AC input voltage range (transfer switch)
Value
180V – 270V
Description
Input voltage range which is accepted by the ePRO Combi for feeding
through to the connected load. Two AC undervoltage values can be set. An
absolute undervoltage level which directly releases the AC transfer switch
when exceeded (factory setting = 150V), and a delayed undervoltage
level, which releases the AC transfer switch after a certain delay (factory
settings are 180V and 5 seconds). The charger stops charging when the AC
input voltage drops below 185V and restarts again above 190V.
Con
fi
gurable by
Dashboard
Parameter
AC input frequency range
Value
45Hz – 65Hz
Description
Input frequency range which is accepted by the ePRO Combi. Can be
set to full range (45Hz – 65Hz), or to a smaller range within the 45Hz
lower and 65Hz upper boundaries.
Con
fi
gurable by
Dashboard