5.
Dynamic Load Balancing
5.1.
DLB system
Dynamic Load Balancing - DLB - is a smart system of
load management used during EV charging process. It
allows dividing the total input power between connec-
tors in a way, that allows maintaining consumption be-
low a given level. It helps to prevent surcharging net-
work of the charger’s operator with extra fees from an
electric power supplier. DLB also allows using avail-
able power, which appears after disconnecting any car
from the charger in the network. It can be used from
the quantity of just two connectors, up to couple of hun-
dreds of them, so it can be applied as well as in the
single household as well as in the whole parking lot.
In the basic version, an internet connection is not nec-
essary for DLB to work.
After energizing chargers,
they’ll know what to do.
Nevertheless, after fitting „master” unit in the Bridge
communication module and Enelion administration sys-
tem, you gain access to many developed functions al-
lowing remote management of charging.
5.2.
Energy Guard - impact on DLB
The combination of EnergyGuard with a network of
chargers allows the DLB functionality to be extended
to include other electrical devices than chargers in the
power distribution. From this point on, the connection
limitation will determine the total power allocated to the
building including chargers. The chargers will adjust the
charging power of the cars so that, together with other
electrical devices, the current limit of the connection will
not be exceeded.
When energy-consuming devices are turned on, the
Energy Guard, measuring the load, transmits the in-
formation about the current energy consumption to the
charging station, thanks to which there is a proportional
reduction of the available power for EV charging - there
is no risk of overloading the home electrical installation,
and thus triggering electrical protection.
Energy Guard can also be used in a network of charg-
ers (parking, shopping centres, fleet parking), which al-
lows you to use the full potential of the current supplied
energy, without increasing it - that is profitable and thus
valued by accountants in every company. During peak
hours, cars can be charged with the minimum required
power adequately distributed by Enelion’s charging ter-
minals. The undoubted advantage of using EEG is the
possibility of having a network of chargers with a total
power exceeding that available - having 22kW available
for chargers, we can have several 22kW chargers that
will always charge with the maximum available power.
Fig. 11: No DLB system
Fig. 12: Active DLB system
When the charging stations are connected to the inter-
net, system status can be monitored and managed via
the administration system Enelink.
5.3.
Configuration
Configuration can be done via DealerToolBox.
This
software is available on the manufacturer website. To
configure the network of chargers, it is necessary to
know the maximum current limit of the connection. Typ-
ically, this parameter corresponds to the tripping value
of the fuse protecting the connection in the switchgear.
Another configuration parameter is the location of the
EnergyGuard measurement in the switchgear. Energy-
Guard can be installed in two ways:
1. The measurement of the whole power network to-
gether with charger stations [Fig.4].
2. The measurement of the whole power network
without charger stations [Fig.5].
INFO
Information on the connection variants with dia-
grams can be found in the chapter
Design indi-
cations of the installation
.
11
Dynamic Load Balancing
Содержание Energy Guard
Страница 1: ...Energy Guard Assembly manual Enelion Sp z o o info enelion com...
Страница 16: ......
Страница 17: ...2021 ENELION Pana Tadeusza 50 80 123 Gdan sk Polska...