Teqwave H
Commissioning
Hauser
53
Parameter overview with brief description
Parameters
Procedure
Selection/input
Factory setting
View options
(transmitter)
Filter options/filter arrangements
(Viewer)
Select filter options and
arrangements to enable or disable
them.
Filter options:
• Measuring range limits
• Calibration range limits
• Stationarity
Filter arrangements:
• Hide measured value
• Background coloring
• Hold measured value
The "Measuring range limits" and
"Calibration range limits" options are
enabled.
The "Stationarity" option is disabled.
Change in analysis parameter 1…n
[unit]
Specify the limit value for the
maximum permissible speed at
which the analysis parameter can
change. Enable or disable the
function using the button.
If the measuring unit is
changed, the unit is changed
according to the "change in"
setting, but the value entered
is not converted.
0.01 … 100 [unit]
100 [unit]
The function is disabled.
Change in temperature °C/min
(°F/min; °K/min)
Specify the limit value for the
maximum permissible speed at
which the temperature can change.
Enable or disable the function using
the button.
If the measuring unit is
changed, the unit is changed
according to the "change in"
setting, and the value entered
is converted.
0.01 … 100 °C/min (K/min) or
0.018… 180 °F/min
1.5 °C/min
The function is enabled.
Change in speed of sound (m/s)/s
Enter the limit value for the
maximum permissible speed at
which the speed of sound can
change. Enable or disable the
function using the button.
0.01 to 100 (m/s)/s
100 (m/s)/s
The function is enabled.
Change in density [unit]
Enter the limit value for the
maximum permissible speed at
which the density can change.
Enable or disable the function using
the button.
If the measuring unit is
changed, the unit is changed
according to the "change in"
setting, and the value entered
is converted.
0.01 to 100 (kg/m3)/s or (g/l)/s
0.00001 to 0.10 (g/cm3)/s
100 (kg/m3)/s
The function is enabled.