Solimotion FTR20
Commissioning
46
Hauser
Function
Description
Default value
6
Limit signal function
7
Switch-on delay
8
Switch-off delay
9
Simulation
―
A
Damping
B
Gain
C
Detection range
D
- has no function -
―
E
- has no function -
―
F
Reset to factory settings
―
8�6
Simulation
The Solimotion FTR20 gives you the ability to simulate a signal and thereby an output
variable, independent of the process, for example, in order to configure a downstream PLC or
a data logger.
The simulation is carried out as follows (function 6 = standard setting):
Move the encoding switch to position 9
→ Display of the function number
→ After 2 seconds: Display of the simulated signal strength
(signal strength = 0 LEDs, switch output: not switched,
current output: 4 mA)
Press the or
key on the device to configure the desired signal strength
→ Display of the changed simulated signal strength, example:
(signal strength = 8 LEDs, switch output: switched,
current output: 16.8 mA)
Move the encoding switch to the initial position 0
→ Display of the current signal strength
The simulation ends as soon as the encoding switch is no longer at position 9.