Solimotion FTR20
Commissioning
44
Hauser
• The delays impact only the switch outputs (relay and solid-state relay); they have no
significance for the current output.
• If the process conditions are unstable, the signal strength can be calmed with a
parameterizable damping (function A).
8�4�4
Damping (function A)
For unstable process conditions, the display of the signal strength can be stabilized by a
configurable damping; averaging of the output signal takes place here over the set time.
27 Example heavy fluctuating material on conveyor belt
Changing conveyor loads can lead to unstable signal strengths; these are stabilized using a
configured damping (averaging over the set time).
Setting
Damping
Setting
Damping
off
2 s
100 ms
3 s
200 ms
5 s
300 ms
10 s
500 ms
20 s
1 s