Output
Number
max. 2
Fault condition
3.5 mA or 22 mA presettable
Effect to NAMUR recommendation NE43
Response time
max. 200 ms (input signal from 10% to 90% FSD)
D/A resolution
Current: 13 bit, Voltage: 13 bit
Number
max. 2
Galvan. isolation
To all other current circuits
Relays
Output signal
Binary, switches on reaching a preset alarm set point value
Number
2
Contact type
1 potential free changeover contact (SPDT)
Contact loading
<= 250 V
AC
, 5 A / 30 V
DC
, 5 A
Alarm set point function
Operating mode
Off, min-, Maximum safety, gradient, alarm
Switch threshold
- 19999 to + 99999
Hysteresis
- 19999 to + 99999
Time delay
0s to 99s
Signal source
Input 1, input 2, mathematics process value
Number
2
Display
1 yellow LED per set point, optional symbol in LC display
Scan rate
100 ms
Mathematics function
Operator
Addition/subtraction/multiplication
Factor 1/2
-19999 to +99999, 0 to 4 decimal points
Input 1/2
Dependent on selected input values
Offset
-19999 to +99999, 0 to 4 decimal points
Power supply
Power supply
90...250 V
AC
50/60 Hz
18...36 V
DC
, 20...28 V
AC
50/60 Hz
Power
consumption
11 VA
Fuse
315 mA, slow blow (90...250 V)
630 mA, slow blow (20...28 V)
Accuracy
Current
Accuracy: 0.1 % FSD
Temperature drift: 0.05 % / 10 K ambient temperature
Analogue output
Accuracy: 0.1 % FSD
Temperature drift: 0.05 % / 10 K ambient temperature
Process transmitter