The new addresses will be added in front of the last value. The
remaining linearisation points should be entered in the new
addresses, independently from their actual sequence.
The added values will again be sorted upwards
within the existing linearisation points before
being saved.
5.7 Operating parameters
Parameter
Setting up selections
Default
settings
Actual
setting
* Alternating pump control
ALT
activate/deactivate the
alternating pump control
YES
activate
NO
deactivate
NO
If two pumps are controlled using the process transmitter, the alternating pump control
enables an even loading of the pumps. If a switch point is reached the pump with the
shortest running time is switched on. If both pumps are operational and a switch off point is
reached then the pump with the longest running time is switched off. The running times are
calculated internally. They are always reset to zero when the alternating pump control is
activated/deactivated or there is a power failure. The alternating pump control should only
be used when both relays are set to
MAX-
or
MIN-
function.
Parameter
Setting up selections
Default
settings
Actual
setting
* Input value (X-axxis)
X1
/
X2
/
XM
Input of sensor value of the
analogue input in
engineering units (X-value)
or the calculated
mathematics value.
Value:
Sensor scale 0% (
SCLO
) to
Sensor scale 100% (
SCHI
)
or
MSCLO
to
MSCHI
at
TAB M
-----
In order to delete the linearisation point the value “
-----
” can be set up.
Keep the push button “+” held down until the value appears.
* Display value
Y1
/
Y2
/
YM
Input of the sensor or
mathematics value allocated
display value (Y-value).
Value:
-19999 to 99999
00000
PARAM
NO101-NO120
NO201-NO220
NOM01-NOM20
Process transmitter
60