![Endress+Hauser RA33 Скачать руководство пользователя страница 68](http://html.mh-extra.com/html/endress-hauser/ra33/ra33_operating-instructions-manual_2407412068.webp)
Appendix
Batch Controller RA33
68
Hauser
Filling stages
510003-00 Two filling stages can be used for accurate dosing of a
batch. A larger-quantity flow rate can be stopped earlier
and the total quantity can be dosed with more accuracy
until the preset counter value is reached using another,
smaller flow.
Switches fill phase 1
510004-00 Specifies the output with which the main filling stage is
controlled.
Switches fill phase 2
510005-00 Specifies which output is used for the filling stage with the
additional, larger flow rate.
Delay phase 2
510006-00 The delay specifies the interval before the second valve
with the larger flow rate is switched.
Pre-stop fill phase 2
510008-00 The advance stop specifies what the remaining quantity is
when filling stage 2 is ended and accurate dosing starts.
Fixed after-run correction
510009-00 Fixed after-run correction is used to compensate for longer
valve closing times and response times in order to achieve
more accurate batching results. It can also be used when
initially teaching the device (even if the automatic after-
run correction function is activated) to ensure that the
after-run quantity is kept to a minimum.
Automatic after-run correc-
tion
510010-00 Automatic after-run correction works in addition to fixed
after-run correction and automatically corrects the accu-
racy to compensate for possible system changes brought
about, e.g., by valve aging.
Max. preset counter
510012-00 Defines the maximum preset counter value that can be
entered in order to prevent the entry of incorrect, high
values.
Batch information
The Batch information menu is used to manage identifiers
and recipes.
Recipe management
510100-00 Recipe management can be activated. The identifier, man-
ual after-run correction and preset counter can thus be
preset for various batches and selected during operation
without setup access.
Number
510101-00 Enter the number of required, preconfigurable recipes
here.
Possible values: 1-30
Batch name
510105-00 Use this option to enter the batch identifier which will
then be stored in the batch report.
Batch no. start value
510110-00 Use this option to enter the start value of the current batch
number.
Reset batch no.
510111-00 Use this option to reset the current number to the start
value.
Recipe 1 to 30
Batch name
510102-00
…-29
Use this option to enter the batch identifier which will
then be stored in the batch report.
Preset counter
510104-00
…-29
This preset counter represents the preconfigured preset
counter value, which is used when the recipe is selected
but can still be modified.
Fixed correction
510109-00
…-29
Fixed after-run correction is used to compensate for longer
valve closing times and response times in order to achieve
more accurate batching results. It can also be used when
initially teaching the device (even if the automatic after-
run correction function is activated) to ensure that the
after-run quantity is kept to a minimum.
Compensation
This menu contains all of the settings for correcting the
volume or converting to mass using additional measured
variables.
Compensation
530000-00 Activate this option to correct the flow volume or to calcu-
late the mass.