Technical data
Batch Controller RA33
54
Hauser
Digital inputs
The digital inputs can be used for external control. A batch run can be started or stopped via these
inputs, or the inputs can prevent a new batch from starting. In addition, the time can also be
synchronized.
10.0.2
Output
Current/pulse output
(optional)
This output can be used either as a 0/4 to 20 mA current output or as a voltage pulse output. The
output is galvanically isolated (500 V testing voltage towards all other inputs and outputs).
Current output
Pulse output
2 x relay output
The relays are designed as NO contacts. The output is galvanically isolated (1500 V testing voltage
towards all other inputs and outputs).
2 x digital output (open
collector, optional)
The two digital inputs are galvanically isolated from one another and from all the other inputs and
outputs (testing voltage: 500 V). The digital outputs can be used as status or pulse outputs. The open
collector outputs are particularly suitable for a high number of switching cycles since, in contrast to
relays, these outputs are non-wearing.
Auxiliary voltage output
(transmitter power supply)
The auxiliary voltage output can be used to power the transmitter or control the digital inputs. The
auxiliary voltage is short-circuit proof and galvanically isolated (500 V testing voltage towards all
other inputs and outputs).
Output range:
0/4 to 20 mA + 10 % over range
Load:
0 to 600
Ω
(as per IEC 61131-2)
Accuracy:
0.1 % of full scale value
Temperature drift:
0.01 %/K (0.056 %/°F) of the full scale value
Inductive load:
Max. 10 mH
Capacitance load:
Max. 10
μ
F
Ripple:
Max. 12 mVpp on 600
Ω
for frequencies < 50 kHz
D/A converter resolution:
14 bit
Frequency:
Max. 12.5 kHz
Pulse width:
Min. 40
μ
s
Voltage level:
Low: 0 to 2 V
High: 15 to 20 V
Maximum output current:
22 mA
Short-circuit proof
Max. relay switching capacity:
AC: 250 V, 3 A
DC: 30 V, 3 A
Minimum contact load:
10 V, 1 mA
Min. switching cycles:
>10
5
Frequency:
Max. 1 kHz
Pulse width:
Min. 500
μ
s
Current:
Max. 120 mA
Voltage:
Max. 30 V
Voltage drop:
Max. 2 V in conductive state
Maximum load resistance:
10 k
Ω
!
Note!
For higher values, the switching edges are flattened.
Output voltage:
24 V DC ±15% (not stabilized)
Output current:
Max. 70 mA
HART
®
signals are not affected.