Batch Controller RA33
Appendix
Hauser
67
Pulse width
310008-00 You can set the pulse width in the range from 0.04 to
1000 ms here.
Numerical value, max. 8 digits including decimal separa-
tor.
!
Note!
Visible only if a user-defined pulse width was selected.
Open Collector 1/2
Settings for the open collector output (pulse or status).
Function
OC 1:
320000-00
OC 2:
320000-01
Specify what the open collector output should output
(pulses or status).
Op. Mode
320001-00
320001-01
Function of the relay:
• NC contact: in the quiescent state, the relay is closed
(maximum safety).
• NO contact: the relay is open in quiescent state.
Channel/value
320002-00
320002-01
Select which channel/value is to be output at the output.
Only for function = pulse output.
Pulse Value
320004-00
320004-01
The pulse value specifies which quantity an output pulse
corresponds to (e.g. 1 pulse = 5 liters).
Pulse width
320005-00
320005-01
The pulse width limits the max. possible output frequency
of the pulse output. Define a fixed or dynamic pulse
width.
Pulse width
320006-00
320006-01
You can set the pulse width in the range from 0.5 to 1000
ms here.
Numerical value, max. 8 digits including decimal separa-
tor.
!
Note!
Visible only if a user-defined pulse width was selected.
Relay
Setup for the selected relay
Op. Mode
330000-00 Function of the relay:
• NC contact: in the quiescent state, the relay is closed
(maximum safety).
• NO contact: the relay is open in quiescent state.
Application
Configure various application-specific settings (e.g. group
settings, limit values, etc.).
Batch settings
Batch active
400010-00 Specifies whether a status signal should be issued at an
output when a batching operation is active
Batch mode
510000-00 There are three batching modes available.
• Batching runs to the end of the preset counter in stan-
dard mode.
• Automatic restart: In this mode, a sequence is started
by the start command and repeats batching until it
ends.
• A preset counter is not required in manual mode;
batching is started and ended locally or via control
input.
Restart delay
510001-00 This time specifies the interval between a completed batch
and an automatically restarted one in the "Autom. restart"
batching mode.
Counting direction
510002-00 The counting direction determines the way the preset
counter is shown on the display. If the direction is for-
wards, the counter is increased from 0 to the preset
counter value; if it is backwards, it is decreased from the
preset counter value to 0.