Proline Promass I 100
Hauser
39
A0023344
Installation in down pipes
However, the following installation suggestion allows for installation in an open vertical pipeline.
Pipe restrictions or the use of an orifice with a smaller cross-section than the nominal diameter
prevent the sensor running empty while measurement is in progress.
1
2
3
4
5
A0015596
17
Installation in a down pipe (e.g. for batching applications)
1
Supply tank
2
Sensor
3
Orifice plate, pipe restriction
4
Valve
5
Batching tank
DN
Ø orifice plate, pipe restriction
[mm]
[in]
[mm]
[in]
8
³⁄₈
6
0.24
15
½
10
0.40
15 FB
½ FB
15
0.60
25
1
14
0.55
25 FB
1 FB
24
0.95
40
1½
22
0.87
40 FB
1½ FB
35
1.38
50
2
28
1.10
50 FB
2 FB
54
2.13
80
3
50
1.97
FB = Full bore