Electrical connection
Proline Promass E 200
30
Hauser
7.3
Hardware settings
7.3.1
Setting the device address
PROFIBUS PA
The address must always be configured for a PROFIBUS DP/PA device. The valid address
range is between 1 and 126. In a PROFIBUS DP/PA network, each address can only be
assigned once. If an address is not configured correctly, the device is not recognized by the
master. All measuring devices are delivered from the factory with the device address 126 and
with the software addressing method.
2
98
3
4
5
6
7
8
1
D
IP
O
N
A0015686
5
Address switch in the connection compartment
Hardware addressing
1. Set switch 8 to the "OFF" position.
2. Using switches 1 to 7, set the address as indicated in the table below.
The change of address takes effect after 10 seconds. The device is restarted.
Switch
1
2
3
4
5
6
7
Value in "ON" position
1
2
4
8
16
32
64
Value in "OFF" position
0
0
0
0
0
0
0