Electrical connection
Proline Promag P 100
22
Hauser
Cable type
Twisted pairs
Loop resistance
≤110 Ω/km
Signal damping
Max. 9 dB over the entire length of the cable cross-section
Shielding
Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.
Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be
used for every transmission rate. Cable type A is recommended.
Cable type
A
Characteristic impedance
135 to 165 Ωat a measuring frequency of 3 to 20 MHz
Cable capacitance
<30 pF/m
Wire cross-section
>0.34 mm
2
(22 AWG)
Cable type
Twisted pairs
Loop resistance
≤110 Ω/km
Signal damping
Max. 9 dB over the entire length of the cable cross-section
Shielding
Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.
EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category for a
cable used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please refer to
the "Media Planning and Installation Manual. EtherNet/IP" of the ODVA Organization.
Cable diameter
• Cable glands supplied:
M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• Spring terminals:
Wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
Содержание Proline Promag P 100
Страница 13: ...Proline Promag P 100 Storage and transport Endress Hauser 13 A0015604 A0015605...
Страница 47: ......
Страница 48: ...www addresses endress com...