Electrical connection
Proline Promag P 100
30
Hauser
1. Set the desired IP address using the corresponding DIP switches on the I/O electronics
module.
Hardware addressing with the configured IP address is enabled after 10 s.
2. Disable software addressing via DIP switch 8 (OFF).
PROFIBUS DP
The address must always be configured for a PROFIBUS DP/PA device. The valid address
range is between 1 and 126. In a PROFIBUS DP/PA network, each address can only be
assigned once. If an address is not configured correctly, the device is not recognized by the
master. All measuring devices are delivered from the factory with the device address 126 and
with the software addressing method.
Setting the address
OFF ON
1
2
3
4
5
6
7
8
9
10
1
2
4
8
16
32
64
- Write protection
- Not used
PROFIBUS
address
- Software addressing
A0021265
13
Addressing using DIP switches on the I/O electronics module
1. Disable software addressing via DIP switch 8 (OFF).
2. Set the desired device address via the corresponding DIP switches 1 to 7.
Example (→ 13, 30): 1 + 16 + 32 = device address 49
The device demands rebooting after 10 s. After rebooting, hardware addressing is
enabled with the configured IP address.
7.3.2
Enabling the terminating resistor
PROFIBUS DP
To avoid incorrect communication transmission caused by impedance mismatch, terminate
the PROFIBUS DP cable correctly at the start and end of the bus segment.