Proline Cubemass C 500
Hauser
25
Configuration of the device
address
• DIP switches on the I/O electronics module
• Via operating tools (e.g. FieldCare)
System integration
Information regarding system integration: Operating Instructions → 107.
• Cyclic data transmission
• Block model
• Description of the modules
EtherNet/IP
Protocol
• The CIP Networks Library Volume 1: Common Industrial Protocol
• The CIP Networks Library Volume 2: EtherNet/IP Adaptation of CIP
Communication type
• 10Base-T
• 100Base-TX
Device profile
Generic device (product type: 0x2B)
Manufacturer ID
0x11
Device type ID
0x103B
Baud rates
Automatic ¹⁰⁄₁₀₀ Mbit with half-duplex and full-duplex detection
Polarity
Auto-polarity for automatic correction of crossed TxD and RxD pairs
Supported CIP connections
Max. 3 connections
Explicit connections
Max. 6 connections
I/O connections
Max. 6 connections (scanner)
Configuration options for
measuring device
• DIP switches on the electronics module for IP addressing
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• Electronic Data Sheet (EDS) integrated in the measuring device
Configuration of the EtherNet
interface
• Speed: 10 MBit, 100 MBit, auto (factory setting)
• Duplex: half-duplex, full-duplex, auto (factory setting)
Configuration of the device
address
• DIP switches on the electronics module for IP addressing (last octet)
• DHCP
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• EtherNet/IP tools, e.g. RSLinx (Rockwell Automation)
Device Level Ring (DLR)
Yes
System integration
Information regarding system integration: Operating Instructions
→ 107.
• Cyclic data transmission
• Block model
• Input and output groups
PROFINET
Protocol
"Application layer protocol for decentral device periphery and distributed
automation", version 2.3
Communication type
100 MBit/s
Conformity class
Conformance Class B
Netload Class
Netload Class II
Baud rates
Automatic 100 Mbit/s with full-duplex detection
Cycle times
From 8 ms
Polarity
Auto-polarity for automatic correction of crossed TxD and RxD pairs
Заказывайте
на
сайте
: www.tinnova.ru/endress_hauser/ ||
Эл
.
почта