Electrical connection
Flowmeter Proline 10 Modbus RS485
14
Hauser
5.3
Connecting the transmitter
5.3.1
Transmitter terminal connections
1
2
3
A0045438
1
Cable entry for power supply cable: supply voltage
2
Cable entry for signal cable
3
Ground terminal, outer
5.3.2
Terminal assignment
The terminal assignment is documented on an adhesive label.
The following terminal assignment is available:
Modbus RS485 and current output 4 to 20 mA (active)
Supply voltage
Output 1
Output 2
1 (+)
2 (–)
26 (+)
27 (–)
24 (+)
25 (–)
22 (B)
23 (A)
L/+
N/–
Current output
4 to 20 mA (active)
–
Modbus RS485
Modbus RS485 and current output 4 to 20 mA (passive)
Supply voltage
Output 1
Output 2
1 (+)
2 (–)
26 (+)
27 (–)
24 (+)
25 (–)
22 (B)
23 (A)
L/+
N/–
–
Current output
4 to 20 mA (passive)
Modbus RS485
5.3.3
Wiring the transmitter
• Use a suitable cable gland for the power supply cable and signal cable.
• Pay attention to the requirements for the power supply cable and signal cable
• Use shielded cables for digital communication.