Commissioning
Option
Description
Bargraph alternating (1M/2M)*
Grenzstand 1
%
068
1M
The percentage values and associated bargraph for
measuring channel 1 (1M) and measuring channel 2 (2M)
are displayed in an alternating display (display duration
approx. 5 seconds each time).
↓↑ 5 seconds
Grenzstand 1
%
025
2M
Tag alternating (1M/2M)*
Grenzstand 1
%
068
1M
Measurement 1
The tag is displayed together with an alternating display
(display duration approx. 5 seconds each time) showing the
percentage value of the level limit detection (measuring
channel 1, 1M) and the bulk flow detection (measuring
channel 2, 2M).
↓↑ 5 seconds
Grenzstand 1
%
025
Measuremen
t 1
2M
8�4�3�4 Back to home
System
3000
→
Display
3500
→
Back to home
3530
This function is used to set the length of time the system will wait following the last time a
button is pressed before the display switches automatically back to the measured value
display.
Options: 3 to 9999 seconds
8�4�3�5 Format display
System
3000
→
Display
3500
→
Format display
3540
This function is used to check the display, all segments are activated for around 2 seconds.
Options: "On", "Abort"
8�4�3�6 Contrast setting
System
3000
→
Display
3500
→
Contrast
3550
This function is used to set the display contrast.
Options: 1 (low contrast) to 7 (high contrast)