30
Nivotester FTR525
Hauser
Commissioning
038
1M
2 1 13
2
1
3
4
19 Manual adjustment upper limit (UL)
1 Current measured value
2 Set detection range (= 0-100% of signal output)
3 Percentage value for the upper limit relative to the maximum possible detection range
4 Upper limit (adjustable using this function)
8�4�1�4 Level limit detection damping
Application
2000
→
Sensor
2100
→
Limit detection
2110
→
Damping
2114
It is possible, for instance in the case of very turbulent processes, to steady the measuring
signal. To do so, a time can be set over which the measured values are averaged.
Options: 100 ms to 20 s, Off
Setting the damping results in a longer reaction time.
8�4�1�5 Automatic setup of motion detection
Application
2000
→
Sensor
2100
→
Motion detection
2120
→
Automatic setup
2121
Automatic setup is carried out with movement of bulk solids either present or not
present (in front of the FDR57 transceiver); the option selected for this corresponds to the
state of the bulk flow.
Options: "With movement", "Without movement"
1 2
FQR57 FDR57
FQR57 FDR57
20 Setup conditions of the motion detection
The following manual adjustment functions can be used to carry out fine adjustment of
the microwave barrier or to suit changing application conditions.
8.4.1.6 Manual adjustment lower limit (LL) motion detection
Application
2000
→
Sensor
2100
→
Motion detection
2120
→
Manual adjustment LL
2122
This function can be used to change the lower limit of the set detection range of the
motion detection (function
2112
→ 28).