Micropilot FMR20 HART
Diagnostics and troubleshooting
Hauser
41
Error
Possible cause
Solution
Device is visible in the
live list but cannot be
accessed via
SmartBlue
Android end
device
Is the location function permitted for the app, was it approved the
first time?
GPS or positioning function must be activated for certain Android
versions in conjunction with Bluetooth
Activate GPS - close the app fully and restart - enable the
positioning function for the app
Device is visible in the
live list but cannot be
accessed via
SmartBlue
Apple end device
Log in as standard
Enter user name "admin"
Enter initial password (device serial number) paying attention to
lower/upper case
Login via SmartBlue
not possible
Device is being put
into operation for
the first time
Enter initial password (device serial number) and change. Pay
attention to lower/upper case when entering the serial number.
Device cannot be
operated via
SmartBlue
Incorrect
password entered
Enter correct password
Device cannot be
operated via
SmartBlue
Password
forgotten
Contact the Hauser Service department
Device cannot be
operated via
SmartBlue
The sensor
temperature is too
high
If the ambient temperature results in an elevated sensor
temperature of >60 °C (140 °F), Bluetooth communication may be
disabled.
Shield the device, isolate it and cool it down if necessary.
TAG in SmartBlue
and HART do not
match
System-related
The device ID (TAG) is transferred to the live list via Bluetooth® to
facilitate device identification. The tag is abbreviated in the middle
since the HART tag can be up to 32 characters long but Bluetooth®
can only use 29 characters as the device name:
e.g: "FMR20N12345678901234567890123456" becomes
"FMR20N12345678~567890123456"
10.3 Diagnostic event in the operating tool
If a diagnostic event is present in the device, the status signal appears in the top left status
area of the operating tool along with the corresponding symbol for the event level in
accordance with NAMUR NE 107:
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
Calling up remedial measures
‣
Navigate to the
Diagnostics
menu
In the
Actual diagnostics
parameter the diagnostic event is shown with event text
10.4 Diagnostic event in the RIA15
A diagnostic event of the FMR20 is not directly shown in the RIA15. The fault F911 only
appears directly on the RIA15 in the event of an FMR20 alarm.
Displaying a FMR20 diagnostic event in the RIA15
1. Navigate to: DIAG/TERR
2. Press
3. Press
4. Press