LPGmass
6
Hauser
Measuring range
Measuring ranges (not custody transfer mode)
DN
Measuring range full scale values
min(F)
to
max(F)
[mm]
[in]
[kg/h]
[lb/min]
8
³⁄₈
0 to 2
000
0 to 73.5
15
½
0 to 6
500
0 to 238
25
1
0 to 18
000
0 to 660
40
1½
0 to 45
000
0 to 1
650
50
2
0 to 70
000
0 to 2
570
The values of the corresponding custody transfer certificate apply in custody transfer mode.
Recommended measuring range
Operable flow range
Over 1000 : 1.
Flow rates above the preset full scale value do not override the electronics unit, with the result that
the totalizer values are registered correctly.
Output
Output signal
Modbus RS485
Physical interface
In accordance with EIA/TIA-485-A standard
Terminating resistor
For device version used in intrinsically safe areas: integrated and can be activated
via DIP switches on the Safety Barrier Promass 100
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Modbus RS485
Failure mode
Choose from:
• NaN value instead of current value
• Last valid value
Interface/protocol
• Via digital communication:
Modbus RS485
• Via service interface
Plain text display
With information on cause and remedial measures
Light emitting diodes (LED)
Status information
Status indicated by various light emitting diodes
The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred