R
Function group
RELAY
Configure
limit contacter
Clean =
Chemoclean
(only with Rel3 and Rel4)
Timer
PID controller
LC °C
= Limit contacter T
=
LC PV
Limit contacter O
2
R2 (5)
R2 (4)
R2 (3)
R2 (2)
R2 (1)
Function
switch on or off
On; Basic; PID+B
R2 (3)
Off;
R231
Entry of set point
0.0 ... 20.00 mg/l
0.0 ... 200 %SAT
5.00 mg/l;
50.0 %SAT;
R232
Entry of
control gain Kp
0.01...20.00
1.00
R233
Entry of integral action time
Tn (0,0 = no I component)
0.0 ... 999.9 min
0.0 s
R234
Function
switch on or off
On
R2 (4)
Off;
R241
Setting of rinse time
0 ... 999 s
30 s
R242
Setting of pause time
1 ... 7200 min
360 min
Setting of minimum
pause time
1 ... 3600 min
120 min
R243
R244
Selection of contact
to be configured
Rel2; Rel3; Rel4
Rel1;
R1
Function
switch on or off
On
R2 (2)
Off:
R221
Entry of
switch-on temperature
60.0 °C
–10.0 ... +60.0 °C
R222
Entry of
switch-off temperature
60.0 °C
–10.0 ... +60.0°C
Setting of
pickup delay
0 ... 2000 s
0 s
R224
R223
Function
switch on or off
On
R2 (1)
Off;
R211
Selection of switch-on
contact point
0 ... 20.00 mg/l
0 ... 200.0 %
20.00 mg/l;
200.0 %;
R212
Selection of switch-off
contact point
0 ... 20.00 mg/l
0 ... 200.0 %
20.00 mg/l;
200.0 %;
R213
Setting of
pickup delay
0 ... 2000 s
0 s
R214
Function
switch on or off
On
R2 (5)
Off;
R251
Entry of pre-rinse time
0 ... 999 s
20 s
R253
Selection of start pulse
ext = external (dig. input 2)
i+ext = in external
i+stp = internal suppr.
by external
int = internal
R252
Function group
SERVICE
S
Selection of language
GER
ITA; FRA
ESP; NEL
ENG;
S1
Hold configuration
=
CAL=during calibration
Setup=during configuration
none = no hold
S+C during configuration
and calibration
S2
Software
Version
SW version
Software
Version
SW version
Software
Version
SW version
E131
Hardware
Version
HW version
Hardware
Version
HW version
Hardware
Version
HW version
E132
Display of
serial number
E133
E134
Software
Version
SW version
E141
Hardware
Version
HW version
E142
Display of
serial number
Display of
Modul-ID
Display of
Modul-ID
Display of
Modul-ID
Display of
Modul-ID
E143
E144
Entry of hold dwell
period
0 ... 999 s
10 s
S4
Manual Hold
On
Off;
S3
Entry of SW-Upgrade
release code
(plus package)
0000 ... 9999
0000
S5
Function group
E+H SERVICE
E
Selection of Modul
Rel = Relay
MainB
= Main board
Trans
= transmitter
Contr
= controller
E111
E112
Display of
serial number
E113
E114
E121
E122
Display of
serial number
E123
E124
Function group
INTERFACE
I
Entry of address
HART or PROFIBUS
I1
E1 (4)
E1 (3)
E1 (2)
E1 (1)
Entry of cleaning time
0 ... 999 s
10 s
R254
I2
Tag description
@@@@@@@@
Appendix
Liquisys M COM 223 F / 253 F
74
Hauser