Liquipoint FTW33
Diagnostics and troubleshooting
Hauser
31
Navigation
Parameter → System → Reset to factory settings (RES)
Description
L
WARNING
Confirming the "Standard Command" with "Reset to factory settings" causes an imme-
diate reset to the factory settings of the order configuration.
If the factory settings have been changed, downstream processes might be affected follow-
ing a reset (the behavior of the switch output or current output might be changed).
‣
Make sure that downstream processes are not started unintentionally.
The reset is not subject to additional locking, such as in the form of device locking. The
reset also depends on the device status.
Any customer-specific configuration carried out at the factory is not affected by a reset
(customer-specific configuration remains).
The following parameters are
not
reset when a reset is performed:
• Minimum µC-temperature
• Maximum µC-temperature
• Last Diagnostic (LST)
• Operating hours
Note
The last error is not reset in a reset.