Liquiphant M/S with electronic insert FEL58 + Nivotester FTL325N
42
Hauser
Commissioning or
proof test report
Report for version I
System-specific data
Company
Measuring point/TAG no.
Facility
Device type/Order code
Serial no. of Liquiphant
Name
Date
Signature
Operating mode, density range and version (please tick appropriate box)
Mode of operation
MIN safety
MAX safety
Density switch
Setting >0.7
Setting >0.5
Version
I
One Liquiphant, no Nivotester
Electronic
insert
FEL56
Electronic
insert
FEL58
Commissioning or proof test report
Test sequence
A
Approach the level
Remove and immerse in a medium of similar density and viscosity
B
Simulation on Liquiphant by pressing the test button
C
Check the switch point under reference operating conditions
Current at terminal 2
Test step
Termin
al
Set point FEL56
Set point FEL58
Actual value
Step 1
(GOOD state)
0.6 to 1.0 mA
2.2 to 3.5 mA
Step 2
(demand mode)
2.2 to 2.8 mA
A, C: 0.6 to 1.0 mA
B: 0 mA
Step 3
(GOOD state)
0.6 to 1.0 mA
2.2 to 3.5 mA
Conclusion
Passed
Failed
1)
Only for Liquiphant with electronic insert FEL58.
2)