iTHERM TrustSens TM371, TM372
Operability
Hauser
17
Submenus and user roles
Certain parts of the menu are assigned to certain user roles. Each user role corresponds to
typical tasks within the lifecycle of the device.
User role
Typical tasks
Menu
Content/meaning
Maintenance
Operator
Commissioning:
• Configuration of the measurement.
• Configuration of data processing (Measurement
range, etc.).
Reading measured values.
Calibration:
• Configuration of the warning and alarm limit values
as well as interval monitoring.
• Configuration and creation of a calibration report
(wizard).
"Setup"
"Calibration"
Contains all parameters for commissioning and
calibration:
•
Setup parameters
Once values have been set for these parameters, the
measurement should generally be completely
configured.
•
Calibration parameters
Contains all information and parameters for the self-
calibration, including a wizard for creating a
calibration report. This wizard is available in the
online parameterization.
Fault elimination:
• Diagnosing and eliminating process errors.
• Interpretation of device error messages and
correcting associated errors.
"Diagnostics"
Contains all parameters for detecting and analyzing
errors:
•
Diagnostic list
Contains up to 3 currently pending diagnostic
messages.
•
Event logbook
Contains the last 5 diagnostic messages (no longer
pending).
•
"Device information" submenu
Contains information for identifying the device.
•
"Measured values" submenu
Contains all current measured values.
•
"Simulation" submenu
Is used to simulate measured values or output values.
•
Diagnostic settings
Configuration of diagnostic behavior and status
signal according to NE107
Expert
Tasks that require detailed knowledge of the function
of the device:
• Commissioning measurements under difficult
conditions.
• Optimal adaptation of the measurement to difficult
conditions.
• Detailed configuration of the communication
interface.
• Error diagnostics in difficult cases.
"Expert"
Contains all parameters of the device (including those
that are already in one of the other menus). The
structure of this menu is based on the function blocks
of the device:
•
"System" submenu
Contains all higher-order device parameters that do
not pertain either to measurement or the measured
value communication.
•
"Output" submenu
Contains all parameters for configuring the analog
current output and the loop check.
•
"Communication" submenu
Contains all parameters for configuring the digital
communication interface.
6.3
Access to the operating menu via an operating tool
6.3.1
FieldCare
Function scope
FDT/DTM-based plant asset management tool from Hauser. It can configure all
smart field units in a system and help you manage them. By using the status information,
it is also a simple but effective way of checking their status and condition. Access takes
place via the HART
®
protocol or CDI (= Hauser Common Data Interface).