Technical Data
TMT180
20
Hauser
Influence of load
• ± 0.02%/100
Ω
Percentages refer to the full scale value
Long-term stability
•
≤
0.18 °F/year (
≤
0.1 °C/year) or
≤
0.05%/year
Values under reference operating conditions. % refer to the set span. The highest value is valid.
10.0.6
Installation conditions
Installation conditions
• Installation angle: no limit
• Installation area: connection head accord. to DIN 43 729 Form B; field housing TAF 10
10.0.7
Environmental conditions
Ambient temperature limits
-40 to 185 °F (-40 to +85 °C)
Storage temperature
-40 to 212 °F (-40 to +100 °C)
Climate class
as per IEC 60654-1, class C
Condensation
allowed
Degree of protection
IP 00, NEMA 4 (IP 66) installed in field housing TAF 10
Shock and vibration resistance
4g / 2 to 150 Hz as per IEC 60 068-2-6
Electromagnetic compatibility
(EMC)
CE Electromagnetic Compatibility Compliance
The device meets all requirements listed under IEC 61326 Amendment 1, 1998
This recommendation is a uniform and practical way of determining whether the devices used in
laboratory and process control are immune to interference with an objective to increase its
functional safety.
Discharge of static electricity
IEC 61000-4-2
6 kV cont., 8 kV air
Electromagnetic fields
IEC 61000-4-3
80 to 2000 Hz
10 V/m
Burst (signal)
IEC 61000-4-4
1 kV
2 kV (B)
1)
1) self
recovery
Transient voltage
IEC 61000-4-5
1 kV unsym. / 0.5 kV sym.
HF coupling
IEC 61000-4-6
0.15 to 80 MHz
10 V