Proline Promag 51
Identification
Hauser
9
2.1.3
Nameplate for connections
A0000963
Fig. 4:
Nameplate specifications for transmitter (example)
1
Serial number
2
Possible configuration of current output
3
Possible configuration of relay contacts
4
Terminal assignment, cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L– for DC
5
Signals present at inputs and outputs, possible configuration and terminal assignment (20 to 27), see also
"Electrical values of inputs/outputs"
6
Version of device software currently installed
7
Installed communication type, e.g.: HART, PROFIBUS etc.
8
Information on current communication software (Device Revision and Device Description), e.g.: Dev. 01 / DD 01
for HART
9
Date of installation
10
Current updates to data specified in points 6 to 9
2.2
Certificates and approvals
The devices are designed to meet state-of-the-art safety requirements in accordance with sound
engineering practice. They have been tested and left the factory in a condition in which they are
safe to operate.
The devices comply with the applicable standards and regulations in accordance with EN 61010-1
"Safety requirements for electrical equipment for measurement, control and laboratory use" and
with the EMC requirements of IEC/EN 61326.
The measuring system described in these Operating Instructions is therefore in conformity with the
statutory requirements of the EC Directives. Hauser confirms successful testing of the
device by affixing to it the CE mark.
The measuring system meets the EMC requirements of the Australian Communications and Media
Authority (ACMA).
Communication:
Drivers:
Device SW:
ID xxxx (HEX)
XX.XX.XX (WEA)
XXXXXXXXXX
Date:
DD.MMM.YYYY
Ex-works / ab-Werk / réglages usine
26(+)
/
27(-)
NC:
Versorgung /
Tension d'alimentation
Observer manuel d'instruction
See operating manual
Betriebsanleitung beachten
Active: 0/4...20mA, RL max. = 700 Ohm
Passive: 4...20mA, max. 30VDC
Passive: 30VDC, 250mA
Active: 24VDC/25mA (max. 250mA/20ms)
Passive: 30VDC, 250mA
(HART: RL.min. = 250 OHM)
fmax = 1kHz
3...30VDC, Ri = 5kOhm
f-OUT
I-OUT (HART)
12345678912
Ser.No.:
Supply /
24(+)
/
25(-)
22(+)
/
23(-)
20(+)
/
21(-)
N/L-
PE
A:
NO:
P:
L1/L+
1
2
319475-00XX
A
P
active
passive
normally open contact
normally closed contact
X
STATUS-OUT
STATUS-IN
X
Update 1
Update 2
2
3
1
4
5
6
7
8
9
10