Troubleshooting
Proline Promag 51
68
Hauser
359
…
362
S: PULSE RANGE
!: # 359 to 362
Pulse output:
Pulse output frequency is out of range.
1.
Increase the setting for pulse weighting.
2.
When selecting the pulse width, choose a value that can still
be processed by a connected counter (e.g. mechanical
counter, PLC etc.).
Determine the pulse width:
– Variant 1: Enter the minimum duration that a pulse must
be present at the connected counter to ensure its
registration.
– Variant 2: Enter the maximum (pulse) frequency as the
half "reciprocal value" that a pulse must be present at the
connected counter to ensure its registration.
Example:
The maximum input frequency of the connected counter is
10 Hz. The pulse width to be entered is:
a0004437
3.
Reduce flow.
Custody transfer mode
If the pulse output is not suitable for custody transfer mode, the
pulse value can be altered via the HART interface or the FieldCare
operating software.
The pulse width can be altered independently of the operation.
No. # 5xx
Application error
501
S: SW.-UPDATE ACT.
!: # 501
New amplifier or communication (I/O module) software
version is loaded.
Currently no other functions are possible.
Wait until the procedure is finished.
The device will restart automatically.
Custody transfer mode
During operation, no software version can be loaded.
502
S: UP-/DOWNLOAD ACT
!: # 502
Uploading or downloading the device data via operating
program.
Currently no other functions are possible.
Wait until the procedure is finished.
Custody transfer mode
Checking via a test device is not possible.
No. # 6xx
Simulation mode active
601
S: POS. ZERO RETURN
!: # 601
Positive zero return active
"
Caution!
This message has the highest display priority!
Switch off positive zero return.
Custody transfer mode
In custody transfer mode, positive zero return cannot be
activated.
611
…
614
S: SIM. CURR. OUT n
!: # 611 to 614
Simulation current output active
Switch off simulation.
Custody transfer mode
Simulation not possible
621
…
624
S: SIM. FREQ. OUT n
!: # 621 to 624
Simulation frequency output active
Switch off simulation.
Custody transfer mode
Simulation not possible
631
…
634
S: SIM. PULSE n
!: # 631 to 634
Simulation pulse output active
Switch off simulation.
Custody transfer mode
Simulation not possible
641
…
644
S: SIM. STAT. OUT n
!: # 641 to 644
Simulation status output active
Switch off simulation.
Custody transfer mode
Simulation not possible
671
…
674
S: SIM. STATUS IN n
!: # 671 to 674
Simulation status input active
Switch off simulation.
Custody transfer mode
Simulation not possible
691
S: SIM. FAILSAFE
!: # 691
Simulation of response to error (outputs) active
Switch off simulation.
Custody transfer mode
Simulation not possible
No.
Error message / Type
Cause
Remedy (spare parts
ä
73ff)
1
2.10 Hz
= 50 ms