Download
You must first move to the "Offline Configure" menu before carrying out a download.
Step
Entry
Display
Significance
0
MATRIX GROUP SEL.
1
Online
2
1
Offline
3
1
Offline Configure
4
1
New Device or
2
Last Device
The data you wish to be transmit to another electronic insert can be collected in this
menu.
1 New Device
→
This option enables a new electronic insert to be calibrated.
2 Last Device
→
This option enables variables to be edited and changed after
an upload.
There are four function keys within this menu:
HELP (F1) -
Online help. Help describes the variable shown in the display
SEND (F2) -
Marks the variable in the display for the download and then
marks the next variable.
EDIT (F3) -
The variable can be edited and is marked for download once
RETURN (F4) is pressed.
SKIP (F4) -
The variable is skipped (not marked for download). The next
variable is then marked.
The "Offline" menu is displayed after the last variable. The parameters are now stored
in the HART Communicator and are ready for a download into an electronic insert.
After marking has been carried out, downloads can be carried out without first
marking the variables again.
Download
(loading data into the
electronic insert)
Step
Entry
Display Significance
0
MATRIX GROUP SEL.
1
Online
Main menu level
2
3
Transfer
Data transfer
Device to Memory
3
2
Memory to Device
Download:
Loading data into electronic insert
Looking for a device
Looking for a device
Download data from
configuration memory
to device
Ready for data transmission
4 F3
[SEND]
Sending data to device
Data now stored in electronic insert
Electronic insert FEC 12 (HART)
6 Diagnosis and Troubleshooting
Hauser
19