Alternative procedure: 
calibration with the
vessel almost full

The level of the vessel must be known as accurately as possible and should be as
high as possible. A level which is too low reduces the accuracy of the upper point
(corresponding to a full vessel). An ammeter must be connected to the electronic
insert at Terminals 4 - 5.

Assuming that the level is at 90 %, the current value corresponding to a 90 % level
must now be determined. The upper current value can be varied by pressing the two
pushbuttons on the right. The following calculation is used:

 The lower current value (= empty vessel, 0 %) is 4 mA.

 The upper current value (= full vessel, 100 %) is 20 mA.

 This gives a measuring range (‘span’) of 16 mA for a change from 0 to 100 % or

a 0.16 mA increase in current for every 1 % rise in level. 

 For a 90 % level this is 90 % x 0.16 mA/% or 14.4 mA. This must be added to the

4 mA to give the current value required: 
14.4 mA + 4 mA = 18.4 mA
(The upper current value can also be used and 
10 % x 0.16 mA/% = 1.6 mA is to be subtracted from 20 mA)

 The value 18.4 mA (check with the ammeter) is set by pressing the two pushbut-

tons on the right. Pressing pushbutton (+) increases the current and pressing
pushbutton (-) decreases the current.

Note!

No indication is given on the green LED when using this variation.

If the operating status is unclear due to an incorrect setting, then all settings should
be reset to factory-set values and the basic calibration carried out again.

Locking the parameters

Press simultaneously the pushbutton for empty calibration (+) and the pushbutton for
full calibration (-). The settings of the electronic insert can now be called up at any
time using the handheld terminal but not changed. This condition is indicated in the
handheld terminal by the appearence of the code 9999 in Menu Level 2 

"EXTENDED

CALIBRATION"

, Field 8 

"SECURITY LOCKING"

 (see Section 5).

Unlocking the
parameters

Press simultaneously the pushbutton for empty calibration (-) and the pushbutton for
full calibration (+). All settings of the electronic insert can now be called up and
changed using the handheld terminal. This condition is indicated in the handheld
terminal by the appearence of the code 12 in Menu Level 2 

"EXTENDED CALIBRATION"

,

Field 8 "

SECURITY LOCKING

" (see Section 5).

Note!

4    Calibrating

Electronic insert FEC 12 (HART)

10

Hauser

Содержание FEC 12

Страница 1: ...Electronic insert FEC 12 with HART Protocol Level Measurement Operating Instructions BA 148F 00 en 07 95 b Software Version 1 x Part No 016700 1000 Hauser Endress The Power of Know How...

Страница 2: ...ents A detailed description of calibration and operation is given in Sections 3 5 Reset to factory settings Linearisation at handheld terminal Unlock parameters Lock parameters Full calibration Empty...

Страница 3: ...Measuring Point 14 5 1 Locking Unlocking Parameters 14 5 2 Tag Number 14 6 Diagnosis and Troubleshooting 15 6 1 Alarms 15 6 2 Simulation 15 6 3 Description of Fault Responses Error Messages 17 6 4 Re...

Страница 4: ...afety requirements on the measuring point as specified in the accompanying certificate Installation commissioning and operation Installation electrical connection commissioning operation and maintenan...

Страница 5: ...Settings empty calibration 4 mA and full calibration 20 mA using pushbuttons on the electronic insert Operates with a linear characteristic as well as with a stored linearisation curve for horizontal...

Страница 6: ...the probe is always connected to Terminal 3 Warning When using the probe in explosion hazardous areas ensure that the type and routing of the intrinsically safe power and signal line is in accordance...

Страница 7: ...fset for empty vessel probe free 0 pF 350 pF Change in capacitance span for full vessel probe covered 10 pF 2000 pF Total capacitance resulting from initial capacitance plus change in capacitance maxi...

Страница 8: ...t the FEC 12 by using the four pushbuttons see Section 4 Basic Operation The pushbuttons marked with increase current and those marked decrease current Punching the pushbuttons produces a step wise ch...

Страница 9: ...e following diagram shows the menu structure of the HART protocol for the FEC 12 electronic insert Each field in the menu structure can be selected using the arrow or numeric keys on the handheld term...

Страница 10: ...ibration is not then required see also Section 6 4 1 Basic Calibration at the FEC 12 Electronic Insert The following entries are required for basic calibration of the electronic insert Type of lineari...

Страница 11: ...der to set the signal current to the 20 mA upper value The green LED lights up to acknowledge that the setting has been accepted Only when the green LED goes out is the correct value of 20 mA shown on...

Страница 12: ...ammeter is set by pressing the two pushbut tons on the right Pressing pushbutton increases the current and pressing pushbutton decreases the current Note No indication is given on the green LED when u...

Страница 13: ...u to the next higher menu with the arrow key Last step Return to the Online menu with F3 HOME Reset factory settings Step Entry Cursor in display at Significance 1 3 SERVICE SIMULATION 2 4 DEFAULT VAL...

Страница 14: ...R Confirms entry value to be transmitted 5 3 FULL CALIBRATION Full calibration 6 100 0 100 0 Vessel is full a 20 mA signal is output at the entered level or volume 7 F4 ENTER Confirms entry value is t...

Страница 15: ...value can be entered here The units are changed from in the SELECT UNIT menu Step Entry Cursor in display at Significance 1 1 CALIBRATION Basic setting 2 6 VALUE FOR 4 mA Value for 4 mA 3 e g 20 0 20...

Страница 16: ...ot apply if the locking was activated at the electronic insert This is indicated by the code number 9999 in the menu field Step Entry Cursor in Display at Significance 1 2 EXTENDED CALIBRATION Extende...

Страница 17: ...ed It can be used for checking the correct processing of probe signals e g in a process control system Simulation may also be necessary for tracing faults No change in level is required to produce a d...

Страница 18: ...1 3 SERVICE SIMULATION Service Simulation 2 7 SIM VOLUME Simulation of volume e g 77 06 Actual measured value is displayed 3 e g 5 00 5 00 Volume to be simulated is entered 4 F4 ENTER Confirms entry v...

Страница 19: ...permitted range 4 0 20 mA or 3 8 20 mA It has no relationship to the measured value 6 4 Replacing the FEC 12 Electronic Insert Note If you want to transmit the settings of the old electronic insert in...

Страница 20: ...RT Communicator handheld terminal The procedure begins with an upload with the data from the old FEC 12 to the handheld terminal Once the upload has been completed a download is is made and all data a...

Страница 21: ...is marked for download once RETURN F4 is pressed SKIP F4 The variable is skipped not marked for download The next variable is then marked The Offline menu is displayed after the last variable The para...

Страница 22: ...56993 Fax 042 50981 Brazil Samson Endress Hauser Ltda Sao Paulo Tel 011 50313455 Fax 011 50313067 Canada Endress Hauser Ltd Burlington Ontario Tel 905 6819292 Fax 905 6819444 Chile Endress Hauser Chi...

Отзывы: