4    Calibrating

This section deals with the basic settings necessary for the electronic insert to
convert capacitance values into correct data on level or volume, which can then be
shown on a display unit (e.g. meter or handheld terminal). 
The electronic insert can carry out basic settings in two ways:

On site at the electronic insert itself or

On the handheld terminal.

The initial basic settings can also be carried out locally at the electronic insert and
then later with the handheld terminal for, e.g. setting the type of linearisation 
(Note: the electronic insert must not be locked). 

Note!

After completing calibration the matrix should then be locked (see Section 5.1).
After locking, all entries can be called up and displayed but no longer changed.

The values entered can be written in the table below so that the identical values can
again be entered if the electronic insert is replaced. A complete recalibration is not
then required (see also Section 6).

4.1   Basic Calibration at the FEC 12 Electronic Insert

The following entries are required for basic calibration of the electronic insert:

Type of linearisation

Empty calibration

Full calibration

Note!

If an initial calibration is not to be carried out, but instead a recalibration of the
system, then a reset the electronic insert first. 

This also applies when it is not clear if the electronic insert is calibrated with factory
settings (see following section). Unwanted settings may result and lead to incorrect
measured values.

Reset (recall of factory
settings)

Press the pushbuttons for empty calibration (-) and for full calibration (-)
simultaneously for approx. 5 s. This produces the following factory settings:

Significance

Factory settings

Entered values

Empty calibration [%]

0.0

Full calibration [%]

100.0

Min. current 4 mA

off

Output damping [s]

1

Value for 4 mA [%]

0.0

Value for 20 mA [%]

100.0

Safety alarm

max (110 %)

Linearisation

linear

Offset [pF]

349.90

Sensitivity [pF/%]

16.49

Set tag number

’--------’

Select unit

%

Note!

Note!

4    Calibrating

Electronic insert FEC 12 (HART)

8

Hauser

Содержание FEC 12

Страница 1: ...Electronic insert FEC 12 with HART Protocol Level Measurement Operating Instructions BA 148F 00 en 07 95 b Software Version 1 x Part No 016700 1000 Hauser Endress The Power of Know How...

Страница 2: ...ents A detailed description of calibration and operation is given in Sections 3 5 Reset to factory settings Linearisation at handheld terminal Unlock parameters Lock parameters Full calibration Empty...

Страница 3: ...Measuring Point 14 5 1 Locking Unlocking Parameters 14 5 2 Tag Number 14 6 Diagnosis and Troubleshooting 15 6 1 Alarms 15 6 2 Simulation 15 6 3 Description of Fault Responses Error Messages 17 6 4 Re...

Страница 4: ...afety requirements on the measuring point as specified in the accompanying certificate Installation commissioning and operation Installation electrical connection commissioning operation and maintenan...

Страница 5: ...Settings empty calibration 4 mA and full calibration 20 mA using pushbuttons on the electronic insert Operates with a linear characteristic as well as with a stored linearisation curve for horizontal...

Страница 6: ...the probe is always connected to Terminal 3 Warning When using the probe in explosion hazardous areas ensure that the type and routing of the intrinsically safe power and signal line is in accordance...

Страница 7: ...fset for empty vessel probe free 0 pF 350 pF Change in capacitance span for full vessel probe covered 10 pF 2000 pF Total capacitance resulting from initial capacitance plus change in capacitance maxi...

Страница 8: ...t the FEC 12 by using the four pushbuttons see Section 4 Basic Operation The pushbuttons marked with increase current and those marked decrease current Punching the pushbuttons produces a step wise ch...

Страница 9: ...e following diagram shows the menu structure of the HART protocol for the FEC 12 electronic insert Each field in the menu structure can be selected using the arrow or numeric keys on the handheld term...

Страница 10: ...ibration is not then required see also Section 6 4 1 Basic Calibration at the FEC 12 Electronic Insert The following entries are required for basic calibration of the electronic insert Type of lineari...

Страница 11: ...der to set the signal current to the 20 mA upper value The green LED lights up to acknowledge that the setting has been accepted Only when the green LED goes out is the correct value of 20 mA shown on...

Страница 12: ...ammeter is set by pressing the two pushbut tons on the right Pressing pushbutton increases the current and pressing pushbutton decreases the current Note No indication is given on the green LED when u...

Страница 13: ...u to the next higher menu with the arrow key Last step Return to the Online menu with F3 HOME Reset factory settings Step Entry Cursor in display at Significance 1 3 SERVICE SIMULATION 2 4 DEFAULT VAL...

Страница 14: ...R Confirms entry value to be transmitted 5 3 FULL CALIBRATION Full calibration 6 100 0 100 0 Vessel is full a 20 mA signal is output at the entered level or volume 7 F4 ENTER Confirms entry value is t...

Страница 15: ...value can be entered here The units are changed from in the SELECT UNIT menu Step Entry Cursor in display at Significance 1 1 CALIBRATION Basic setting 2 6 VALUE FOR 4 mA Value for 4 mA 3 e g 20 0 20...

Страница 16: ...ot apply if the locking was activated at the electronic insert This is indicated by the code number 9999 in the menu field Step Entry Cursor in Display at Significance 1 2 EXTENDED CALIBRATION Extende...

Страница 17: ...ed It can be used for checking the correct processing of probe signals e g in a process control system Simulation may also be necessary for tracing faults No change in level is required to produce a d...

Страница 18: ...1 3 SERVICE SIMULATION Service Simulation 2 7 SIM VOLUME Simulation of volume e g 77 06 Actual measured value is displayed 3 e g 5 00 5 00 Volume to be simulated is entered 4 F4 ENTER Confirms entry v...

Страница 19: ...permitted range 4 0 20 mA or 3 8 20 mA It has no relationship to the measured value 6 4 Replacing the FEC 12 Electronic Insert Note If you want to transmit the settings of the old electronic insert in...

Страница 20: ...RT Communicator handheld terminal The procedure begins with an upload with the data from the old FEC 12 to the handheld terminal Once the upload has been completed a download is is made and all data a...

Страница 21: ...is marked for download once RETURN F4 is pressed SKIP F4 The variable is skipped not marked for download The next variable is then marked The Offline menu is displayed after the last variable The para...

Страница 22: ...56993 Fax 042 50981 Brazil Samson Endress Hauser Ltda Sao Paulo Tel 011 50313455 Fax 011 50313067 Canada Endress Hauser Ltd Burlington Ontario Tel 905 6819292 Fax 905 6819444 Chile Endress Hauser Chi...

Отзывы: